User Instructions
10 
Power Up 
The CM-6 cycles through an internal self-test cycle for the first minute that it is powered. The unit will execute the test cycle any time 
power is dropped and reapplied (i.e. power failure). During the self-test cycle the unit will display the firmware version number, then 
count down from 60 to 0 (if the display setting is “On”) and finally go into normal operation. The alarm relay will be activated for 10 
seconds and the fan relay for 60 seconds during the power-up cycle unless the “Power Up Test” (PUt) option is OFF. The indicator light 
(LED) will flash green during the self-test cycle. At the end of the 1 minute cycle, the unit will take its first sample of the air and the 
indicator light will turn solid green. 
Operation 
1.  With the display function turned “On”, the CM-6 will show the current concentration of CO ppm or “0” (zero) in clean air. When 
the CO concentration reaches the Fan Relay setting (35 ppm, for example) the display will flash back and forth between “FAn” 
and “35”. With the display function turned ”Off”, the display does not show the CO concentration, but will show “FAn” as long as 
the fan relay is activated. 
2.  With the display function turned “On” and the CO concentration reaching the Alarm Relay setting, (200 ppm, for example) the 
display will flash back and forth between “ALr” and “200”. The buzzer will sound indicating “Alarm” if the buzzer is turned “On”. 
With the display function turned off the display does not show the CO concentration, but will show “ALr” when the Alarm relay is 
activated. 
3.  With the 4-20 mA function turned “On” and the CO concentration climbing, the 4-20 mA signal will ramp up corresponding to 
the concentration (0-200 ppm, for example). The display will show “FAn” and “ALr” and sound as outlined above. 
Default Configuration – Factory Settings 
  The default Power Up Test setting is On 
  The default Display setting is Off 
  The default Buzzer setting is Off 
  The default Alarm Relay Setting is activation at 200 ppm 
  The default Alarm Relay Configuration setting is Normally Open 
  The default Fan Relay Setting is activation at 35 ppm 
  The default Fan Relay Delay setting is 3 minutes 
  The default Fan Relay Runtime setting is 0 
  The default Fan Relay Latching condition is OFF 
  The default Trouble Fan Setting condition is OFF 
  The default 4-20mA Output setting is On 
To change settings, remove the Philips screw on the front of the CM-6. Pull off the front cover of the unit. 