User Manual
16 
display the error code, the green status indicator LED light will flash and the buzzer will chirp intermittently. The Fan relay will also 
engage if the Trouble Fan Setting Option is set to “ON”. 
Operation Test 
Check that the green CM-12 status indicator LED light is illuminated continuously. If not, do not proceed with the tests. If the unit is in 
error mode contact your local representative or Macurco technical service representative for information on resolving the problem. 
1.  Remove the single screw in the middle of the front cover of the CM-12. 
2.  Remove the front cover. 
3.  Observe the LED light on the front of the CM-12. 
4.  If the light is solid green proceed to step 6. 
5.  If the green status indicator LED light is off or flashing, refer to the General section above. 
6.  Locate the switch labeled ENTER/TEST on the left side of the printed circuit board. Press the Test switch once. 
7.  The CM-12 will step through a cycle test: 
a.  The display progresses through the BUZ (Buzzer Test) Art (alarm relay test), Frt (fan relay test) then 
42t (4-20 mA output test). Make sure that the settings are “on” or not disabled “diS”. 
b.  During the first 10 seconds of the test cycle, the display will show BUZ and set off the audible buzzer 
c.  The alarm relay will be closed, so any devices connected to that relay will be tested. 
d.  The Fan relay will be activated for the next 1 minute of the test, so if the fan circuits are wired in the 
normal manner, the fan should run. 
e.  The 4-20mA output will then ramp up from 4 to 16 mA over the next 130 seconds of the test, so if the 
circuit is wired in the normal manner, the control panel or building automation system should respond. 
f.  At the end of the test cycle, the light will turn green and be on steady (Normal Operation), the fan & 
alarm relay will be in standby mode and the 4-20 mA output will return to 4 mA (in clean air). 
8.  When testing is completed reassemble the unit or units. 
Manual Operation Test 
This option gives the user the opportunity to manually initiate an individual test for each relay, the analog output and the sensor 
response to gas. From normal operation mode press the Next button 3 times to get to the Test Mode (tSt). Press the Enter button once 
to get into the Test Menu. Press the Next button to scroll through the four test options and press Enter to initiate the selected test. Note 
that if the relay or 4–20 mA output has been disabled, the test selection will not be displayed in the test menu. 
Art - Alarm Relay Test, 10 seconds 
Frt - Fan Relay Test, 60 seconds 
42t - 420 loop test, 25 seconds 
gtS - Gas Test, 3 minutes (no output to the panel during the gas test) 
The display will flash during the test, or in the case of the gas test, the gas level will alternate with gtS. Once the test is complete, the 
display will return to steady display. To exit the test menu, press the Next button until “End” is displayed then, press Enter to return to 
normal mode.  