Default Configuration – Factory Settings 
  The default Power Up Test setting is On 
  The default Display setting is Off 
  The default Buzzer setting is Off 
  The default Alarm Relay Setting is activation at 200 ppm 
  The default Alarm Relay Configuration setting is Normally Open 
  The default Fan Relay Setting is activation at 35 ppm 
  The default Fan Relay Delay setting is 3 minutes 
  The default Fan Relay Runtime setting is 0 
  The default Fan Relay Latching condition is OFF 
  The default Trouble Fan Setting condition is OFF 
  The default 4-20mA Output setting is On 
To change settings, remove the Philips screw on the front of the CM-12. Pull off the front cover of the unit. 
Selecting Default Configuration – “dEF” 
To select the Default Configuration, in normal mode, push the Next button to get to “Con” or the Configuration menu. Then push the 
Enter button to enter the Con menu. The first selection is the “dEF” or Default setting. Push Enter. If it is already in Default 
configuration, there will be no action. If it is not already in Default configuration, “nO” will be displayed. Push Next to change it to “YES” 
(flashing) then push Enter to confirm the change (solid) and push Enter again to return to “dEF” in the con menu. Push Next until “End” 
is displayed then push Enter to get back to normal operation. 