Manual
Table Of Contents
- Macurco_CD-12xx_Manual(REV. A)
- 1 GENERAL SAFETY INFORMATION
- 2 USER INSTRUCTIONS AND LIMITATIONS
- 3 INSTALLATION AND OPERATING INSTRUCTIONS
- 3.1 Location
- 3.2 General Wiring Information
- 3.3 Mains Power Connection
- 3.4 Fan Relay Connection
- 3.5 Alarm Relay Connection
- 3.6 4-20mA Signal Connection
- 3.7 Installation
- 3.8 Power Up
- 3.9 Operation
- 3.10 Default Configuration – Factory Settings
- 3.10.1 Selecting Default Configuration – “dEF”
- 3.10.2 Selecting Power Up Test Option – “PUt”
- 3.10.3 Selecting Display Option – “dSP”
- 3.10.4 Selecting Buzzer Option – “bUZ”
- 3.10.5 Selecting Alarm Relay Setting – “ArS”
- 3.10.6 Selecting Alarm Relay Configuration – “Arc”
- 3.10.7 Selecting Fan Relay Settings – “FrS”
- 3.10.8 Selecting Fan Relay Delay – “Frd”
- 3.10.9 Selecting Fan Relay Minimum Runtime – “Frr”
- 3.10.10 Selecting Fan Relay Latching Option – “FrL”
- 3.10.11 Selecting Trouble Fan Setting Option – “tFS”
- 3.10.12 Selecting 4-20mA Output Option – “420”
- 3.11 Onboard Diagnostics
- 4 Maintenance
- 5 Appendix A – Menu Structure
- 6 MACURCO PRODUCTS LIMITED WARRANTY
- Macurco_CD-12xx_Manual(REV. A)Canadian_French
- 1 INFORMATIONS GÉNÉRALES DE SÉCURITÉ
- 2 INSTRUCTIONS ET LIMITES D'UTILISATION
- 3 INSTRUCTONS D’INSTALLATION ET D'UTILISATION
- 3.1 Emplacement
- 3.2 Informations générales de câblage
- 3.3 Raccordement de l’alimentation principal
- 3.4 Raccordement du relais de ventilateur
- 3.5 Raccordement du relais d'alarme
- 3.6 Raccordement du signal 4-20 mA
- 3.7 Installation
- 3.7.1 Diagramme pour un courant d'alimentation du relais de commande du ventilateur compris entre 4 et 20 mA
- 3.7.2 Raccordement de base au réseau électrique d'une pièce
- 3.7.3 Raccordement du détecteur à un tableau d'alarme
- 3.7.4 Raccordements de dispositifs CD-12 en cascade
- 3.7.5 Câblage du panneau de contrôle DVP-120
- 3.7.6 Branchement alternatif sur tableau de commande
- 3.8 Mettre en marche
- 3.9 Opération
- 3.10 Configuration par défaut - Paramètres usine
- 3.10.1 Sélection configuration par défaut - "dEF"
- 3.10.2 Sélection d’option de démarrage Test - "PUt"
- 3.10.3 Sélection d’option d'affichage - "dSP"
- 3.10.4 Sélection d’option alarme - "bUZ"
- 3.10.5 Sélection réglage du relais d'alarme – "ArS"
- 3.10.6 Sélection de configuration du Relais Alarme - "Arc"
- 3.10.7 Sélection des paramètres de relais ventilateur - "FrS"
- 3.10.8 Sélection de relais ventilateur retardé - "Frd"
- 3.10.9 Sélection relais de ventilateur d'exécution - "Frr"
- 3.10.10 Sélection de relais de ventilateur, option de verrouillage - "FrL"
- 3.10.11 Sélection de ventilateur de condition de trouble option - "tFS"
- 3.10.12 Sélection 4-20mA Option de sortie - "420"
- 3.11 Systèmes de diagnostic
- 4 Entretien
- 5 Annexe A – Structure de menu
- 6 GARANTIE LIMITÉE DES PRODUITS MACURCO
- Macurco_CD-12xx_Manual(REV. A)Spanish
- 1 Información general de seguridad
- 2 Instrucciones y limitaciones del usuario
- 3 Instrucciones de instalación y funcionamiento
- 3.1 Ubicación
- 3.2 Información general del cableado
- 3.3 Conexión de alimentación de red
- 3.4 Conexión del relé del ventilador
- 3.5 Conexión de relé de alarma
- 3.6 conexión de la señal 4-20mA
- 3.7 Instalación
- 3.8 Encendido
- 3.9 Operación
- 3.10 Configuración predeterminada: configuración de fábrica
- 3.10.1 Seleccionando Configuración predeterminada – "Def”
- 3.10.2 Selección de la opción de prueba de encendido – "Poner”
- 3.10.3 Selección de la opción de visualización – "DSP”
- 3.10.4 Selección de la opción zumbador – "Buz”
- 3.10.5 Selección del ajuste del relé de alarma – "ARS”
- 3.10.6 Selección de la configuración de relé de alarma – "Arc"
- 3.10.7 Selección de los ajustes del relé del ventilador – "FRS”
- 3.10.8 Selección del retardo del relé del ventilador – "FRD”
- 3.10.9 Selección de la duración mínima del relé del ventilador – "FRR”
- 3.10.10 Selección de la opción de bloqueo del relé del ventilador – "FRL”
- 3.10.11 Selección de problemas opción de ajuste del ventilador – "TFS”
- 3.10.12 Selección de la opción de salida 4-20mA-"420"
- 3.11 Diagnóstico a bordo
- 4 Mantenimiento
- 5 Apéndice A – estructura del menú
- 6 Garantía limitada de productos MACURCO
3
1 GENERAL SAFETY INFORMATION
1.1 Intended Use
The Macurco CD-12H and CD-12MC are line voltage, dual relay Carbon Dioxide (CO
2
) detector, controller, and transducer. The CD-
12”x” has selectable 4-20 mA output, buzzer and digital display options. It is an electronic detection system used to measure the
concentration of Carbon Dioxide and provide feedback and automatic ventilation control to help reduce CO
2
concentrations in conference
rooms, classrooms, meeting halls or similar applications. The CD-12”x” is a low-level meter capable of displaying from 0-5000 ppm (parts
per million) of Carbon dioxide. The CD-12”x” is factory calibrated and 100% tested for proper operation.
The CD-12H uses an automated background calibration program to set the clean air level on a regular basis.
The CD-12MC has the same setting and features of the CD-12H with the addition of being able to perform a manual calibration. The CD-
12MC requires a manual calibration process at a minimum of once per year using the Macurco CD6-FCK calibration kit.
1.2 List of Warnings and Cautions within these User Instructions
WARNING
• Each person using this equipment must read and understand the information in these User Instructions before use. Use of this
equipment by untrained or unqualified persons or use that is not in accordance with these User Instructions, may adversely
affect product performance and result in serious injury or death.
• Use only for monitoring the gas which the sensor and instrument are designed to monitor. Failure to do so may result in
exposures to gases not detectable and cause serious injury or death. For proper use, see supervisor or User Instructions,
or call Technical Support at 844-325-3050.
• This equipment may not function effectively below 32°F or above 122°F (0°C or above 50°C). Using the detector outside of
this temperature range may adversely affect product performance and result in serious injury or death.
• This detector helps monitor for the presence and concentration level of a certain specified airborne gas. Misuse may produce
an inaccurate reading, which means that higher levels of the gas being monitored may be present and could result in
overexposure and cause serious injury or death. For proper use, see supervisor or User Instructions, or call Technical
Support at 844-325-3050.
• High voltage terminals (120/240 VAC) are located within this detector, presenting a hazard to service technicians. Only
qualified technicians should open the detector case and service the internal circuits. Ensure power is de-energized from the
detector relays prior to servicing the unit. Failure to do so may result in serious injury or death.
• Do not disassemble unit or attempt to repair or modify any component of this instrument. This instrument contains no user
serviceable parts, and substitution of components may impair product performance and result in serious injury or death.
• Using a certified gas with a concentration other than the one listed for this detector when conducting a calibration verification
test (bump test) will produce inaccurate readings. This means that higher levels of the gas being monitored may be present
and could result in overexposure and cause serious injury or death. For proper use, see supervisor or User Instructions, or
call Technical Support at 844-325-3050
• The following steps must be performed when conducting a calibration verification test (bump test) to ensure proper
performance of the monitor. Failure to do so may adversely affect product performance and result in serious injury or death.
When performing a calibration verification test (bump test) only use certified calibration gas at the required concentration level.
o Do not test with expired calibration gas.
o Do not cover or obstruct display or visual alarm cover.
o Ensure sensor inlets are unobstructed and are free of debris