Manual
Table Of Contents
- Macurco_CD-12xx_Manual(REV. A)
- 1 GENERAL SAFETY INFORMATION
- 2 USER INSTRUCTIONS AND LIMITATIONS
- 3 INSTALLATION AND OPERATING INSTRUCTIONS
- 3.1 Location
- 3.2 General Wiring Information
- 3.3 Mains Power Connection
- 3.4 Fan Relay Connection
- 3.5 Alarm Relay Connection
- 3.6 4-20mA Signal Connection
- 3.7 Installation
- 3.8 Power Up
- 3.9 Operation
- 3.10 Default Configuration – Factory Settings
- 3.10.1 Selecting Default Configuration – “dEF”
- 3.10.2 Selecting Power Up Test Option – “PUt”
- 3.10.3 Selecting Display Option – “dSP”
- 3.10.4 Selecting Buzzer Option – “bUZ”
- 3.10.5 Selecting Alarm Relay Setting – “ArS”
- 3.10.6 Selecting Alarm Relay Configuration – “Arc”
- 3.10.7 Selecting Fan Relay Settings – “FrS”
- 3.10.8 Selecting Fan Relay Delay – “Frd”
- 3.10.9 Selecting Fan Relay Minimum Runtime – “Frr”
- 3.10.10 Selecting Fan Relay Latching Option – “FrL”
- 3.10.11 Selecting Trouble Fan Setting Option – “tFS”
- 3.10.12 Selecting 4-20mA Output Option – “420”
- 3.11 Onboard Diagnostics
- 4 Maintenance
- 5 Appendix A – Menu Structure
- 6 MACURCO PRODUCTS LIMITED WARRANTY
- Macurco_CD-12xx_Manual(REV. A)Canadian_French
- 1 INFORMATIONS GÉNÉRALES DE SÉCURITÉ
- 2 INSTRUCTIONS ET LIMITES D'UTILISATION
- 3 INSTRUCTONS D’INSTALLATION ET D'UTILISATION
- 3.1 Emplacement
- 3.2 Informations générales de câblage
- 3.3 Raccordement de l’alimentation principal
- 3.4 Raccordement du relais de ventilateur
- 3.5 Raccordement du relais d'alarme
- 3.6 Raccordement du signal 4-20 mA
- 3.7 Installation
- 3.7.1 Diagramme pour un courant d'alimentation du relais de commande du ventilateur compris entre 4 et 20 mA
- 3.7.2 Raccordement de base au réseau électrique d'une pièce
- 3.7.3 Raccordement du détecteur à un tableau d'alarme
- 3.7.4 Raccordements de dispositifs CD-12 en cascade
- 3.7.5 Câblage du panneau de contrôle DVP-120
- 3.7.6 Branchement alternatif sur tableau de commande
- 3.8 Mettre en marche
- 3.9 Opération
- 3.10 Configuration par défaut - Paramètres usine
- 3.10.1 Sélection configuration par défaut - "dEF"
- 3.10.2 Sélection d’option de démarrage Test - "PUt"
- 3.10.3 Sélection d’option d'affichage - "dSP"
- 3.10.4 Sélection d’option alarme - "bUZ"
- 3.10.5 Sélection réglage du relais d'alarme – "ArS"
- 3.10.6 Sélection de configuration du Relais Alarme - "Arc"
- 3.10.7 Sélection des paramètres de relais ventilateur - "FrS"
- 3.10.8 Sélection de relais ventilateur retardé - "Frd"
- 3.10.9 Sélection relais de ventilateur d'exécution - "Frr"
- 3.10.10 Sélection de relais de ventilateur, option de verrouillage - "FrL"
- 3.10.11 Sélection de ventilateur de condition de trouble option - "tFS"
- 3.10.12 Sélection 4-20mA Option de sortie - "420"
- 3.11 Systèmes de diagnostic
- 4 Entretien
- 5 Annexe A – Structure de menu
- 6 GARANTIE LIMITÉE DES PRODUITS MACURCO
- Macurco_CD-12xx_Manual(REV. A)Spanish
- 1 Información general de seguridad
- 2 Instrucciones y limitaciones del usuario
- 3 Instrucciones de instalación y funcionamiento
- 3.1 Ubicación
- 3.2 Información general del cableado
- 3.3 Conexión de alimentación de red
- 3.4 Conexión del relé del ventilador
- 3.5 Conexión de relé de alarma
- 3.6 conexión de la señal 4-20mA
- 3.7 Instalación
- 3.8 Encendido
- 3.9 Operación
- 3.10 Configuración predeterminada: configuración de fábrica
- 3.10.1 Seleccionando Configuración predeterminada – "Def”
- 3.10.2 Selección de la opción de prueba de encendido – "Poner”
- 3.10.3 Selección de la opción de visualización – "DSP”
- 3.10.4 Selección de la opción zumbador – "Buz”
- 3.10.5 Selección del ajuste del relé de alarma – "ARS”
- 3.10.6 Selección de la configuración de relé de alarma – "Arc"
- 3.10.7 Selección de los ajustes del relé del ventilador – "FRS”
- 3.10.8 Selección del retardo del relé del ventilador – "FRD”
- 3.10.9 Selección de la duración mínima del relé del ventilador – "FRR”
- 3.10.10 Selección de la opción de bloqueo del relé del ventilador – "FRL”
- 3.10.11 Selección de problemas opción de ajuste del ventilador – "TFS”
- 3.10.12 Selección de la opción de salida 4-20mA-"420"
- 3.11 Diagnóstico a bordo
- 4 Mantenimiento
- 5 Apéndice A – estructura del menú
- 6 Garantía limitada de productos MACURCO
14
If the error mode repeats frequently, check for continuous power and proper voltage. If power is not the problem and a unit has
repeating error conditions, it may need to be returned to Macurco for service, per these User Instructions.
If the error mode indicates “Sensor expired” see section 4.1 End-of-life Signal of these User Instructions.
4 Maintenance
The CD-12”x” is low maintenance. The unit uses a long life NDIR sensor that has a 15-year life expectancy (in normal conditions). The
CD-12H uses an automated background calibration program to set the clean air level on a regular basis. The CD-12H will maintain
accuracy if it is exposed to the “clean air reference value” (this reference value is the lowest concentration to which the sensor is exposed)
at least once per week.
Note: This applies when used in the typical indoor ambient air with weekly unoccupied periods.
All maintenance and repair of products manufactured by Macurco are to be performed at the appropriate Macurco manufacturing facility.
Macurco does not sanction any third-party repair facilities.
Note: There is not a field calibration procedure for the Macurco CD-12H.
4.1 End-of-life Signal
The CD-12”x” has a long life, the non-replaceable infrared sensor (IR Sensor). Fifteen (15) years after the CD-12”x” is installed the sensor
end-of-life signal will be activated indicating that the CD-12”x” has reached the end of its typical usable life. The end-of-life signal will
cause an error code t200 “Sensor expired”. See section 3.6.2 Error Codes
. The end-of-life signal can be silenced for 48 hours by pressing
the "ENTER/TEST" button or by temporarily dropping power to the unit. The end-of-life signal provides the user an opportunity to test
and/or calibrate the sensor (CD-12MC only) assuring that it is still performing within acceptable parameters though the sensor is nearing
the end of its expected life. The silence function will continue to be available for 29 days after the CD-12”x” initiates the initial end-of-life
signal. After this 29-day period, the CD-12”x” can no longer be silenced and the unit must be replaced.
WARNING
Do not disassemble unit or attempt to repair or modify any component of this instrument. This instrument contains no user serviceable
parts and substitution of components may impair intrinsic safety, which may adversely affect product performance and result in
sickness or death.
CAUTION
Avoid the use of harsh cleaning materials, abrasives and other organic solvents. Such materials may permanently scratch the surfaces
and damage the display window, labels, sensor or instrument housing. High voltage terminals (100-240VAC) are located within this
detector, presenting a hazard to service technicians. Only qualified technicians should open the detector case and service the internal
circuits. Ensure power is removed from the detector prior to cleaning the unit. Failure to do so may result in serious injury or death.
4.2 Cleaning
Cleaning of the external surfaces is best carried out using a damp cloth with a mild detergent or soap. Use a vacuum cleaner with a soft
brush to remove dust or contamination under the cover. Do not blow out the sensor with compressed air.
4.3 Testing
WARNING
Using a certified gas with a concentration other than the one listed for this detector when conducting a calibration verification test (bump
test) will produce inaccurate readings. This means that higher levels of the gas being monitored may be present and could result in
overexposure and cause sickness or death. For proper use, see supervisor or User Instructions, or call Technical Support at
844-325-3050.