Manual
Table Of Contents
- Macurco_CD-12xx_Manual(REV. A)
- 1 GENERAL SAFETY INFORMATION
- 2 USER INSTRUCTIONS AND LIMITATIONS
- 3 INSTALLATION AND OPERATING INSTRUCTIONS
- 3.1 Location
- 3.2 General Wiring Information
- 3.3 Mains Power Connection
- 3.4 Fan Relay Connection
- 3.5 Alarm Relay Connection
- 3.6 4-20mA Signal Connection
- 3.7 Installation
- 3.8 Power Up
- 3.9 Operation
- 3.10 Default Configuration – Factory Settings
- 3.10.1 Selecting Default Configuration – “dEF”
- 3.10.2 Selecting Power Up Test Option – “PUt”
- 3.10.3 Selecting Display Option – “dSP”
- 3.10.4 Selecting Buzzer Option – “bUZ”
- 3.10.5 Selecting Alarm Relay Setting – “ArS”
- 3.10.6 Selecting Alarm Relay Configuration – “Arc”
- 3.10.7 Selecting Fan Relay Settings – “FrS”
- 3.10.8 Selecting Fan Relay Delay – “Frd”
- 3.10.9 Selecting Fan Relay Minimum Runtime – “Frr”
- 3.10.10 Selecting Fan Relay Latching Option – “FrL”
- 3.10.11 Selecting Trouble Fan Setting Option – “tFS”
- 3.10.12 Selecting 4-20mA Output Option – “420”
- 3.11 Onboard Diagnostics
- 4 Maintenance
- 5 Appendix A – Menu Structure
- 6 MACURCO PRODUCTS LIMITED WARRANTY
- Macurco_CD-12xx_Manual(REV. A)Canadian_French
- 1 INFORMATIONS GÉNÉRALES DE SÉCURITÉ
- 2 INSTRUCTIONS ET LIMITES D'UTILISATION
- 3 INSTRUCTONS D’INSTALLATION ET D'UTILISATION
- 3.1 Emplacement
- 3.2 Informations générales de câblage
- 3.3 Raccordement de l’alimentation principal
- 3.4 Raccordement du relais de ventilateur
- 3.5 Raccordement du relais d'alarme
- 3.6 Raccordement du signal 4-20 mA
- 3.7 Installation
- 3.7.1 Diagramme pour un courant d'alimentation du relais de commande du ventilateur compris entre 4 et 20 mA
- 3.7.2 Raccordement de base au réseau électrique d'une pièce
- 3.7.3 Raccordement du détecteur à un tableau d'alarme
- 3.7.4 Raccordements de dispositifs CD-12 en cascade
- 3.7.5 Câblage du panneau de contrôle DVP-120
- 3.7.6 Branchement alternatif sur tableau de commande
- 3.8 Mettre en marche
- 3.9 Opération
- 3.10 Configuration par défaut - Paramètres usine
- 3.10.1 Sélection configuration par défaut - "dEF"
- 3.10.2 Sélection d’option de démarrage Test - "PUt"
- 3.10.3 Sélection d’option d'affichage - "dSP"
- 3.10.4 Sélection d’option alarme - "bUZ"
- 3.10.5 Sélection réglage du relais d'alarme – "ArS"
- 3.10.6 Sélection de configuration du Relais Alarme - "Arc"
- 3.10.7 Sélection des paramètres de relais ventilateur - "FrS"
- 3.10.8 Sélection de relais ventilateur retardé - "Frd"
- 3.10.9 Sélection relais de ventilateur d'exécution - "Frr"
- 3.10.10 Sélection de relais de ventilateur, option de verrouillage - "FrL"
- 3.10.11 Sélection de ventilateur de condition de trouble option - "tFS"
- 3.10.12 Sélection 4-20mA Option de sortie - "420"
- 3.11 Systèmes de diagnostic
- 4 Entretien
- 5 Annexe A – Structure de menu
- 6 GARANTIE LIMITÉE DES PRODUITS MACURCO
- Macurco_CD-12xx_Manual(REV. A)Spanish
- 1 Información general de seguridad
- 2 Instrucciones y limitaciones del usuario
- 3 Instrucciones de instalación y funcionamiento
- 3.1 Ubicación
- 3.2 Información general del cableado
- 3.3 Conexión de alimentación de red
- 3.4 Conexión del relé del ventilador
- 3.5 Conexión de relé de alarma
- 3.6 conexión de la señal 4-20mA
- 3.7 Instalación
- 3.8 Encendido
- 3.9 Operación
- 3.10 Configuración predeterminada: configuración de fábrica
- 3.10.1 Seleccionando Configuración predeterminada – "Def”
- 3.10.2 Selección de la opción de prueba de encendido – "Poner”
- 3.10.3 Selección de la opción de visualización – "DSP”
- 3.10.4 Selección de la opción zumbador – "Buz”
- 3.10.5 Selección del ajuste del relé de alarma – "ARS”
- 3.10.6 Selección de la configuración de relé de alarma – "Arc"
- 3.10.7 Selección de los ajustes del relé del ventilador – "FRS”
- 3.10.8 Selección del retardo del relé del ventilador – "FRD”
- 3.10.9 Selección de la duración mínima del relé del ventilador – "FRR”
- 3.10.10 Selección de la opción de bloqueo del relé del ventilador – "FRL”
- 3.10.11 Selección de problemas opción de ajuste del ventilador – "TFS”
- 3.10.12 Selección de la opción de salida 4-20mA-"420"
- 3.11 Diagnóstico a bordo
- 4 Mantenimiento
- 5 Apéndice A – estructura del menú
- 6 Garantía limitada de productos MACURCO
13
Then push the Enter button to enter the Con menu. The ninth selection is the “Frr” or Fan Minimum Run Time. Push Next seven
times to get to “Frr” then Enter. If the runtime is “0” (disabled) push Next to change it to 3, 5, 10 or 15 minutes (flashing) then push
Enter to confirm the change (solid) and push Enter again to return to “Frr” in the Con menu. Push Next until “End” is displayed then
push Enter to get back to normal operation.
3.10.10 Selecting Fan Relay Latching Option – “FrL”
To select the Fan Relay Latching Option, in normal mode, push the Next button to get to “Con” or the Configuration menu. Then push
the Enter button to enter the Con menu. The tenth selection is the “FrL” or Fan Relay Latching Option. Push Next nine times to get to
“FrL” then Enter. If latching is “OFF” push Next to turn it to “ON” (flashing) then push Enter to confirm the change (solid) and push
Enter again to return to “FrL” in the Con menu. Push Next until “End” is displayed then push Enter to get back to normal operation.
3.10.11 Selecting Trouble Fan Setting Option – “tFS”
To select the Trouble Fan Setting Option, in normal mode, push the Next button to get to “Con” or the Configuration menu. Then
push the Enter button to enter the Con menu. The eleventh selection is the “tFS” or Trouble Fan Setting Option. Push Next ten times
to get to “tFS” then Enter. If Trouble Fan Setting is “OFF” push Next to turn it to “ON” (flashing) then push Enter to confirm the change
(solid) and push Enter again to return to “tFS” in the Con menu. Push Next until “End” is displayed then push Enter to get back to
normal operation.
3.10.12 Selecting 4-20mA Output Option – “420”
To select the 4-20mA Output Option, in normal mode, push the Next button to get to “Con” or the Configuration menu. Then push the
Enter button to enter the Con menu. The twelfth selection is the “420” or 4-20mA Output Option. Push Next eleven times to get to
“420” then Enter. If the 4-20mA is “On” push Next to turn it to “OFF” (flashing) then push Enter to confirm the change (solid) and push
Enter again to return to “420” in the Con menu. Push Next until “End” is displayed then push Enter to get back to normal operation.
3.11 Onboard Diagnostics
The CD-12”x” monitors all critical functions of the unit through software diagnostics that continuously test and verify unit operations. If a
problem is found, the unit will switch to a fail-safe/error mode or trouble condition. In this error mode, the Alarm relay will be activated,
the 4-20 mA current loop will go to 24 mA, the unit will display the error code, the green status indicator LED light will flash and the
buzzer will chirp intermittently. The Fan relay will also engage if the Trouble Fan Setting Option is set to “ON”. This is a safety
precaution. To clear this mode, simply turn off power to the unit for a few seconds or push the ENTER/TEST switch (inside the unit).
This will cause the unit to restart the 1-minute self-test cycle.
The 4-20 mA signal can be used for troubleshooting:
• 0 mA is most likely a connection problem
• 4-20 mA is normal gas reading range (0-5000 ppm)
• 24 mA indicates a Trouble condition
Error Codes
• t001 - Trouble with the sensor signal
• t002 - Temperature compensation failed
• t004 - EEPROM bad checksum
• t008 - IR lamp trouble
• t010 - Bad EEPROM
• t020 - Bad calibration
• t040 - Factory calibration failure
• t080 - ADC trouble
• t
100 - Under range
• t200 - Sensor expired
• t400 - Pressure sensor trouble
• t800 - PCBA not tested