MECHANICAL
SPECIFICATIONS
These hoses have been specially designed for operating conditions in
heating and air conditioning, the elastomer is not sensitive to Glycol or water
treatment products.
Each hose is made up of several quality components and the special
crimping on the ferrule under strict quality control gives this hose security against
any leakage.
The special EPDM core meets a fully dened specication: Shore
hardness, resistance to ageing, mechanical resistance (elasticity, tensile fracture,
stretching), ability to accept chemical agents in contact with the elastomer and
non-toxic. ASTM Fire rated hoses meet 25/50 ammability and smoke
development classication requirements of codes and specications when tested
by ASTM E 84 method.
HOSES ARE DESIGNED FOR HYDRONIC HEATING/COOLING, NOT FOR GAS.
Temperature Ratings:
Specs for application and installation:
Max. Operating & Burst Pressure Rating:
Dimensional Information & Material Specifications:
Typical Specications:
½” - 1” MNPT x Female swivel NPSM Male Cone x
Hose Adaptor (Gasket Less Connection)
1-1/4” - 2” MNPT X Female swivel Male x BA-U Gasket
& Hose Adaptor
*Adaptor connections : Male NPT, Female NPT &
Copper Swt.
1/2” 375 PSI OP/ 1500 PSI BP
3/4” 300 PSI OP / 1200 PSI BP
1” 225 PSI OP / 900 PSI BP
Model # Size HCA HCB HCC HCD HCE HCF
12” LENGTH
18” LENGTH
24” LENGTH
36” LENGTH
1/2”
1/2”
1/2”
1/2”
NA
1-1/4”
1-1/4”
1-1/4”
NA
1-1/2”
1-1/2”
1-1/2”
NA
NA
2”
2”
3/4”
3/4”
3/4”
3/4”
HCi-20/1-11
Stainless St eel AISI 304
Stainless St eel AISI 304
Machined Brass / Nickel Plated Brass
BA-U Fiber Washer
Formulated EPDM
External Braiding:
Crimping Ferrules:
Connectors:
Fiber Gasket:
Core:
Furnish and install where indicated on plans Flexible Connectors
as provided by Macon Balancing
Hoses shall be temperature rated: 5
Deg. T o 230 Deg. F. Pressured rated from 375 PSI to 150 PSI based on hose diameter . Constructed specically for operating conditions in heating and
air conditioning with solid brass connectors, stainless steel ferrules, AISI 304 stainless steel braid, and formulated EPDM inner core design to not be
sensitive to Glycol or water treatment products. Hoses shall meet 25/50 ammability and smoke development classication requirements of codes and
specications when tested by ASTM E 84 method.
JOB:
REP:
ENGINEER:
CONTRACTOR:
1-1/4” 200 PSI OP / 800 PSI BP
1-1/2” 175 PSI OP / 600 PSI BP
2” 150 PSI OP / 500 PSI BP
1”
1”
1”
1”
All Sizes: 5 Deg. F to 230 Deg. F
Less than 41 Deg. F with use of Glycol additive.
1. ON INSTALLATION : Avoid absolutely any tension
due to stretching, twisting or torsion during the course of
tightening the connectors.
A. Install and tighten the xed male connector (if
applicable)
B. Install and tighten the union adaptor (if applicable)
C. Install and tighten the swivel nut
Use two spanners in order to screw in the union: One to
hold the hexagon of the adaptor. The other to tighten
the nut at the same time.
IMPORTANT - Do not re-screw the xed connector or
adaptor after tightening of the swivel nut; this will cause
tensioning of the exible with a risk of rapid deterioration
at this point. On removal, take the same precautions. If
the exible incorporates two xed connectors, at least
one must be installed on a counter-part tted with a
screw connector.
*BEFORE INSTALLING REFER TO THE
INSTALLATION & OPERATION INSTRUCTIONS FOR
COMPLETE DETAILS. WARNING: FAILURE TO
FOLLOW THE INSTALLATION & OPERATION
INSTRUCTIONS COULD RESULT IN IMPROPER
INSTALLATION.
innovative hydronic c omponents a nd a cc ess ories for the H VAC industry.
7243 Miller Drive - S uite 200 - W arren, MI 48092 P hone: 1-800-313-HVAC F ax: 1 -866-340-0991
This specication is provided for reference only. HCi reserves the right to change any portion of this specication without notice and without incurring obligation to
make such changes to HCi products previously and subsequently sold.
Gasket Less Swivel Connection ½” -1”
BA-U Fiber Gasket 1-1/4” - 2”
CV* ½” 3/4” 1” 1-1/4” 1-1/2” 2”
12” LENGTH
18” LENGTH
24” LENGTH
36” LENGTH
Note the CV factor is the ow rate, in GPM through the hose at 1 PSID
3.3
3.2
3.1
3.0
NA
37.9
36.9
34.7
NA
64.4
61.0
55.0
NA
NA
110.7
100.8
11.0
10.7
9.9
9.3
20.9
20.3
19.5
18.2
Tunstall Corporation