Specifications
Mac Victor 2.0 Installation Operation Manual 120711.pdf - © 2008 Mac Victor Power, LLC. Page 22 of 23
7 – SPECIFICATIONS
7.1 Mac Victor 2.0 Specifications
7.2 UPS Specifications and Compatible UPS Models
• Capacity: 2kVA (2000VA) straight & locking blade / 3kVA (3000VA) locking blade only
• Input:
- 120Vac, 60hz, 1ph - 20A circuit breaker (2kVA)
- 120Vac, 60hz, 1ph - 30A circuit breaker (3kVA)
- Input SPD (Surge Protection Device) replaceable plug-in module type
• Output:
- 120Vac, 60hz, 1ph - 4 circuit breakers (20A) with Line and Neutral
conductors pre-wired to output terminal strips for hard wiring to remotely
located Isolated Ground (IG) receptacles for critical electronics
- Isolated Ground bar and Chassis Ground bar for proper IG & ground wiring
- Output line conditioner includes low impedance isolation transformer,
electrical noise filtering, and output SPD (Surge Protection Device)
- Optional 5
th
circuit breaker (20A) for integrated IG receptacles (4 outlets)
• Operating Characteristics:
- Overall dimensions - 19”w x 15.75”h x 9.5”d (not including UPS)
- Weight: 85 lbs. (2kVA) / 105 lbs. (3kVA)
- Temperature: 0 - 30º C (32-86º F)
- Humidity: 0% - 90% RH (non – condensing)
• Listings / Patents:
- U.L. 1778 Listed 4
th
Edition – UPS Maintenance Bypass / Line Conditioner
Accessory. The Mac Victor 2.0 is considered a “separately derived source” for
the termination of Isolated Ground conductors per the National Electrical Code.
- U.S. Patents 7,408,271 (11/5/2008) & 7,847,430 (12/7/2010)
• Product Features:
- Plug & receptacle connectivity to many Uninterruptible Power Supply (UPS) vendors
- UPS battery bypass switch (normal/bypass) – “Make before Break” type
- Provides clean, isolated power for all loads (even in the UPS bypass switch mode)
- Front Monitor Display alarms for Input SPD module & Output SPD fuse
- Input & Output pilot lights on front panel for power status diagnostics
- Input & Output power monitoring dry contacts (form C) for remote signaling
- Conduit knockouts (1/2” & 3/4" concentric) on sides, top, bottom, & back
- Remote switch capability provides output power off for fire emergency compliance
• Options:
- 5
th
output circuit breaker (20A) for integrated IG receptacles (4 outlets)
- Remote emergency shutdown of 5
th
circuit / integrated IG receptacles
See the UPS Specifications and Installation/Operation Manual from the UPS manufacturer.
List of Mac Victor 2.0 Compatible UPS Models:
Manufacturer 2kVA Model # 3kVA Model #
General Electric GT2000T * or ** GT3000T
Liebert / Emerson GXT2-2000RT120 * GXT2-3000RT120
Eaton Powerware PW9130-2000 * PW9130-3000
* = use with MVP-2KS All 3kVA UPS use with MVP-3KL
** = use with MVP-2KL
CAUTION: Important UPS limitations
UPS External Battery cabinets are not permitted on the Mac Victor 2.0 Shelf and must be located separately
Maximum UPS width = 8.6 inches / Maximum UPS weight = 95 lbs.
UPS installed on top of the
mounting shelf
See UPS Manual for exact
dimensions
Typical height is 14” – 17”
Maximum width = 8.6”
19”
Figure 7.1
9.5”
15.75”