User manual

BA SC9840knx Anwendungsprogramm HM, DE GB - 23265 - ED - V02
INSTRUCTION MANUAL ENGLISH - PAGE 1 / 4
ENGLISH
Application program
„SC 98.40 knx„
Usage: KNX yearly time switch SC 98.40 knx
Usage:
The time switch can send following datapoints to the bus:
Switching [1 bit]: Time dependent switching
Priority [2 bit]: Priority/control based switching
Value [1 byte]: Transmits a 1 byte integer number
Value [2 byte]: Transmits a 2 byte integer number
Float [2 byte]: Transmits a 2 byte floating point number
Float [4 byte]: Transmits a 4 byte floating point number
Scene control [1 byte]: Up to 64 scenes
HVAC [1 byte]: Heating, ventilating and air conditioning
4x Logic Gates: With AND/OR/XOR and/or with FEEDBACK LOOP. Up to 4 different input values
possible which can be internal (time switch, output of other logic gates) and external
(from the bus) 1 bit values. Output can be 1 bit and 1 byte data values.
Please note:
For operation and installation refer to the instruction manual of the time switch!
Synchronization of DST-change may take up to 1 minute.
Please take into account the resolution of the 2-byte data types (please check the KNX specification)!
Numbers can be entered as follows: E.g. 2e1 = 20 or e.g. 4,321e3 = 4321
Technical data: KNX yearly time switch SC 98.40 knx
Power Supply:
via KNX bus voltage (nominal voltage 29V)
Bus current:
max. 25 mA
Bus system:
KNX
Type of protection:
IP 20 to DIN EN 60529
Permitted ambient temp.:
-30°C … 55°C
Certification mark:
CE
Housing:
self-extinguishing thermoplast
Assembly:
35 mm section rails (DIN EN 60715)
Type of connection:
KNX bus terminal
Rights to technical amendments reserved
Application program
Manufacturer:
Hugo Müller GmbH & Co KG
Program name:
Test Project SC98.40 knx V1.8
Installation:
Please install the application program as test project!
Communication objects 1 - 51
Number
Name
Datentyp
0
Date
11.001 Date
1
Time
10.001 Time of day
3
Request date/time
1.017 1 Bit
4
Switch channel A
1.001 1 Bit
5
Switch channel B
1.001 1 Bit
6
Switch channel C
1.001 1 Bit
7
Switch channel D
1.001 1 Bit
8
Priority Channel A
2.* 2 Bit
9
Priority Channel B
2.* 2 Bit
10
Priority Channel C
2.* 2 Bit
11
Priority Channel D
2.* 2 Bit
12
Integer 1 byte channel A
5.* 1 Byte
13
Integer 1 byte channel B
5.* 1 Byte
14
Integer 1 byte channel C
5.* 1 Byte
15
Integer 1 byte channel D
5.* 1 Byte
16
Integer 2 byte channel A
7.* 2 Byte
17
Integer 2 byte channel B
7.* 2 Byte
18
Integer 2 byte channel C
7.* 2 Byte
19
Integer 2 byte channel D
7.* 2 Byte
20
Float 2 byte channel A
9.* 2 Byte
21
Float 2 byte channel B
9.* 2 Byte
22
Float 2 byte channel C
9.* 2 Byte
23
Float 2 byte channel D
9.* 2 Byte
24
Float 4 byte channel A
14.* 4 Byte
25
Float 4 byte channel B
14.* 4 Byte
26
Float 4 byte channel C
14.* 4 Byte
27
Float 4 byte channel D
14.* 4 Byte
28
Scene channel A
17.001 Scene no.
29
Scene channel B
17.001 Scene no.
30
Scene channel C
17.001 Scene no.
31
Scene channel D
17.001 Scene no.
32
HVAC channel A
20.102 HVAC
33
HVAC channel B
20.102 HVAC
34
HVAC channel C
20.102 HVAC
35
HVAC channel D
20.102 HVAC
36
Priority value channel A OFF
1.003 1 Bit
37
Priority value channel A ON
1.003 1 Bit
38
Priority value channel B OFF
1.003 1 Bit
39
Priority value channel B ON
1.003 1 Bit
40
Priority value channel C OFF
1.003 1 Bit
41
Priority value channel C ON
1.003 1 Bit
42
Priority value channel D OFF
1.003 1 Bit
43
Priority value channel D ON
1.003 1 Bit
44
Integer value 1 byte channel A OFF
5.* 1 Byte
45
Integer value 1 byte channel A ON
5.* 1 Byte
46
Integer value 1 byte channel B OFF
5.* 1 Byte
47
Integer value 1 byte channel B ON
5.* 1 Byte
48
Integer value 1 byte channel C OFF
5.* 1 Byte
49
Integer value 1 byte channel C ON
5.* 1 Byte
50
Integer value 1 byte channel D OFF
5.* 1 Byte
51
Integer value 1 byte channel D ON
5.* 1 Byte