Instructions
TECHNICAL MANUAL GS 3x.10 KNX – ENGLISH
7
Number Name Object function C R
W T U Objekt size Data type
64
DEWP: Dew point alarm enabled (switching object)
output
C
-
-
T
-
1 Bit
switching
64 DEWP: Dew point alarm enabled (priority) output C - - T - 2 Bit priority switching
64 DEWP: Dew point alarm enabled (0...100%) output C - - T - 1 Byte percent (0...100%)
64 DEWP: Dew point alarm enabled (0...255) output C - - T - 1 Byte counter pulses (0...255)
64 DEWP: Dew point alarm enabled Scene (1...64) output C - - T - 1 Byte Scenen Nummer
65 DEWP: Request dew point temperature input C - W - - 1 Bit trigger
66 P: Air pressure absolute [Pa] output C - - T - 2 Bytes 2-Byte float value, Druck (Pa)
67 P: Air pressure relative [Pa] output C - - T - 2 Bytes 2-Byte float value, Druck (Pa)
68 P: Air pressure sensor error output C - - T - 1 Bit Boolean
69 P: Request absolute air pressure input C - W - - 1 Bit trigger
70 P: Request relative air pressure input C - W - - 1 Bit trigger
71 VAVR: Control value (0...255) output C - - T - 1 Byte counter pulses (0...255)
71 VAVR: Control value (0...100%) output C - - T - 1 Byte percent (0...100%)
81 E1 switching sensor output C - - T - 1 Bit switching
81 E1 Alarm sensor output C - - T - 1 Bit 1-Bit, Alarm
81 E1 switching output C - - T - 1 Bit switching
81 E1 Blinds UP/DOWN output C - - T - 1 Bit up/down
81 E1 Switch (event 0) output C - - T - 1 Bit switching
81 E1 Priority (event 0) output C - - T - 2 Bit priority switching
81 E1 1-Byte value (-128...127) (Event 0) output C - - T - 1 Byte 8-Bit unsigned value, counter pulses (0...255)
81
E1 1-Byte value (0...255) (Event 0)
output
C
-
-
T
-
1 Byte
counter pulses (0...255)
81 E1 Scene (Event 0) output C - - T - 1 Byte scene control
81 E1 2-Byte value (-32.768...32.767) (Event 0) output C - - T - 2 Bytes 2-Byte signed value, pulses difference
81
E1 2-Byte value (0...65.535) (Event 0)
output
C
-
-
T
-
2 Bytes
2-Byte unsigned value, pulse
81 E1 4-Byte value (-2.147.483.648...2.147.483.647) (Event 0) output C - - T - 4 Bytes 4-Byte signed value, counter pulses
81 E1 4-Byte value (0...4.294.967.295) (Event 0) output C - - T - 4 Bytes 4-Byte unsigned value, counter pulses
81 E1 2-Byte Floating point (Event 0) output C - - T - 2 Bytes float value, Temperature (°C)
81 E1 Scene output C - - T - 1 Byte scene control
81 E1 switching level 1 output C - - T - 1 Bit switching
81 E1 switching 1 actuation output C - - T - 1 Bit switching
81 E1 HZ: Counter reading 1-Byte-value output C - - T - 1 Byte 8-Bit unsigned value, counter pulses (0...255)
81 E1 HZ: Counter reading 1-Byte-value output C - - T - 1 Byte counter pulses (0...255)
81 E1 HZ: Counter reading 2-Byte-value output C - - T - 2 Bytes 2-Byte signed value, pulses difference
81 E1 HZ: Counter reading 2-Byte-value output C - - T - 2 Bytes 2-Byte unsigned value, pulse
81 E1 HZ: Counter reading 4-Byte-value output C - - T - 4 Bytes 4-Byte signed value, counter pulses