Instructions

TECHNICAL MANUAL GS 3x.10 KNX ENGLISH
6
Number Name Object function C R
W T U Objekt size Data type
41
RTR: Eco increment when cooling
input
C
-
W
-
-
2 Bytes
float value, Temperature (°C)
42 RTR: Current set point temperature output C - - T - 2 Bytes float value, Temperature (°C)
43 RTR: Comfort temperature +/- 0,1K input C - W - - 1 Bit up/down
44 RTR: Standby setback when heating +/- 0,1K input C - W - - 1 Bit up/down
45 RTR: Eco Setback when heating +/- 0,1K input C - W - - 1 Bit up/down
46 RTR: Standby increment when cooling +/- 0,1K input C - W - - 1 Bit up/down
47 RTR: Eco increment when cooling +/- 0,1K input C - W - - 1 Bit up/down
48 RTR: HVAC mode: 1=comf, 2=stdb, 3=eco output/input C - - - - 1 Byte HVAC mode
49 RTR: Comfort mode enabled input C - W - - 1 Bit trigger
50 RTR: Standby mode enabled input C - W - - 1 Bit trigger
51 RTR: Eco mode enabled input C - W - - 1 Bit trigger
52 RTR: Status heating output C - - T - 1 Bit switching
53 RTR: Status cooling output C - - T - 1 Bit switching
54 RTR: Control value main level heating output C - - T - 1 Byte counter pulses (0...255)
54 RTR: Control value main level heating output C - - T - 1 Byte percent (0...100%)
54 RTR: Control value main level heating output C - - T - 1 Bit switching
54 RTR: Control value main level heating output C - - T - 1 Bit switching
55 RTR: Control value extra level heating output C - - T - 1 Byte counter pulses (0...255)
55 RTR: Control value extra level heating output C - - T - 1 Byte percent (0...100%)
55 RTR: Control value extra level heating output C - - T - 1 Bit switching
55
RTR: Control value extra level heating
output
C
-
-
T
-
1 Bit
switching
56 RTR: Control value main level cooling output C - - T - 1 Byte counter pulses (0...255)
56 RTR: Control value main level cooling output C - - T - 1 Byte percent (0...100%)
56
RTR: Control value main level cooling
output
C
-
-
T
-
1 Bit
switching
56 RTR: Control value main level cooling output C - - T - 1 Bit switching
57 RTR: Control value extra level cooling output C - - T - 1 Byte counter pulses (0...255)
57 RTR: Control value extra level cooling output C - - T - 1 Byte percent (0...100%)
57 RTR: Control value extra level cooling output C - - T - 1 Bit switching
57 RTR: Control value extra level cooling output C - - T - 1 Bit switching
58 RTR: Guide value [°C] input C - W - - 2 Bytes float value, Temperature (°C)
59 RTR: Blocking object heating input C - W - - 1 Bit enable
60 RTR: Blocking object cooling input C - W - - 1 Bit enable
61 RTR: Blocking object extra level heating input C - W - - 1 Bit enable
62 RTR: Blocking object extra level cooling input C - W - - 1 Bit enable
63 DEWP: Dew point temperature [°C] output C - - T - 2 Bytes float value, Temperature (°C)