Instructions

TECHNICAL MANUAL GS 3x.10 KNX ENGLISH
5
Communication objects
Number
Name
Object function
C
R
W
T
U
Objekt size
Data type
1 Send ‘0’ in operation output C - - T - 1 Bit Boolean
1 Send ‘1’ in operation output C - - T - 1 Bit Boolean
2 Request status input C - W - - 1 Bit switching
16 rF: Humidity value [%] output C - - T - 2 Bytes humidity (%)
17 rF: Humidity value (1 Byte) [%] output C - - T - 1 Byte percent (0...100%)
18 rF: Humidity value external [%] input C - W - - 2 Bytes humidity (%)
19 rF: Request humidity value input C - W - - 1 Bit trigger
20 rF: Sensor error output C - - T - 1 Bit Boolean
21 RFR: Control value (0...255) output C - - T - 1 Byte counter pulses (0...255)
21 RFR: Control value (0...100%) output C - - T - 1 Byte percent (0...100%)
21
RFR: Scene (1…64)
output
C
-
-
T
-
1 Byte
Scenen Nummer
22 RFR: Control value level 1 (switching object) output C - - T - 1 Bit switching
22 RFR: Control value level 1 (priority) output C - - T - 2 Bit priority switching
23
RFR: Control value level 2 (switching object)
output
C
-
-
T
-
1 Bit
switching
23 RFR: Control value level 2 (priority) output C - - T - 2 Bit priority switching
24 RFR: Control value level 3 (switching object) output C - - T - 1 Bit switching
24 RFR: Control value level 3 (priority) output C - - T - 2 Bit priority switching
25 RFR: Base set point [%] input C - W - - 2 Bytes humidity (%)
26 RFR: Base set point (1 Byte) [%] input C - W - - 1 Byte percent (0...100%)
27 RFR: Blocking object threshold 1 input C - W - - 1 Bit enable
28 RFR: Blocking object threshold 2 input C - W - - 1 Bit enable
29 RFR: Blocking object threshold 3 input C - W - - 1 Bit enable
30 RFR: Blocking object input C - W - - 1 Bit enable
30 RFR: Blocking object input C - W - - 1 Bit enable
31 T: Temperature value [°C] output C - - T - 2 Bytes float value, Temperature (°C)
32 T: Temperature value external [°C] input C - W - - 2 Bytes float value, Temperature (°C)
33 T: Request temperature value input C - W - - 1 Bit trigger
34 T: Sensor error output C - - T - 1 Bit Boolean
35 T: Heat alarm output C - - T - 1 Bit Boolean
36 T: Frost alarm output C - - T - 1 Bit Boolean
37
RTR: Comfort temperature
input
C
-
W
-
-
2 Bytes
float value, Temperature (°C)
38 RTR: Standby setback when heating input C - W - - 2 Bytes float value, Temperature (°C)
39 RTR: Eco setback when heating input C - W - - 2 Bytes float value, Temperature (°C)
40
RTR: Standby increment when cooling
input
C
-
W
-
-
2 Bytes
float value, Temperature (°C)