Table 5
Sealant Usage
Interior Installation
Sealant
Application
Supplier Model Color
Max.
Temp.
Joints DuraVent S-650 Red 650°F
Inner Flue DuraVent S-2000 White 2000°F
Exterior Installation
Sealant
Application
Supplier Model Color
Max.
Temp.
Joints DuraVent S-650 Red 650°F
Outer Band DuraVent S-375 Gray 375°F
CAUTION
DO NOT ALLOW SCREWS TO PENETRATE
THE INNER FLUE. THIS CAN CAUSE
CORROSION, GAS LEAKAGE OR EXPANSION
FAILURE. NEVER USE SCREWS THROUGH
THE OUTER CASING OF AN ADJUSTABLE
LENGTH OR EXPANSION JOINT. OBSERVE
ADEQUATE SAFETY MEASURES WHEN
USING A DEGREASER.
Table 6
Maximum Chimney Heights and Support Method for Model DIS and DAS
Inside Diameter
Anchor Plate Anchor Plate Ventilated (APV) Wall Support (WS)
Tee (T)
Building Metal
Frame
Building Metal
Frame
Building Wood
Frame
Building Metal
Frame
Building Wood
Frame
5 147 133 133 147 61 105
6 128 116 116 128 53 92
8 103 93 93 103 43 74
10 86 78 78 86 35 61
12 73 66 66 73 30 53
14 64 58 58 64 27 46
16 57 52 52 57 24 41
18 53 48 48 53 22 38
20 48 43 43 48 20 34
22 44 40 40 44 18 31
24 37 34 34 37 15 27
26 35 32 32 35 14 25
28 33 30 30 33 13 23
30 31 28 28 31 13 22
32 29 26 26 29 12 21
34 27 25 25 27 11 20
36 26 23 23 26 11 18