User Manual
24
SECTION E TERMINATIONS, STARTING
ADAPTORS, DRAIN LENGTH AND RELIEF
VALVE
STARTING ADAPTORS
Single Wall Adaptor (SWA)
1. The Single Wall Adaptor is used as an
appliance connector. It is designed to be
clamped with a Retaining Band and a locking
band over a shank type ue gas outlet.
2. First, slide the retaining band over the
appliance outlet and tighten it with supplied
bolt. (See Figure 37).
3. Add a bead of sealant about 1/8” on the
ange of the retaining band and one on the
ange of the adaptor (SWA) and mate those
two anges together. Be sure to ll all the
gaps with S-2000 sealant. (See Figure
38 and Figure 39).
4. Tighten the Locking Band to hold and seal
the adaptor in place. See Figure 40 for
typical installation.
ANSI Flange Adaptor (FA)
1. The Flange Adaptor (FA) is intended for use
as a connection to a class 125 or 150 ANSI
pipe ange.
2. This type of connection requires a ange
gasket and bolt set provided by the installer.
The gasket and bolts are typically sold by
pipe, valve and ttings houses as ‘NBG’ set.
Figure 41 illustrates a typical installation.
3. An outer band with insulation is included
to close the installation.
Flanged Adapter (FHA)
1. The Flanged Adaptor (FHA) is used to
connect the DIS / DAS chimney to anged
appliance outlets other than those with ANSI
pipe anges.
2. The adaptor is designed to sandwich an 1/2
inch ange between two half ring and the
appliance anged outlet. The Flange Adaptor
comes with beam clamps to clamp the FHA
to the appliance. See Figure 42.
Figure 37
Figure 37a
Figure 38
Figure 38a
Appliance Outlet
Insert and Tighten
the Band in Place
Insert and Tighten
the Band in Place
Inlet
Apply Bead
of Sealant
Apply Bead
of Sealant
Inlet
Appliance Outlet