Instructions / Assembly
GFCI Receptacles
• Self-testing technology
allows GFCI to automatically
check proper operation every
30seconds
• LEDs indicate status of GFCI
protection function
• Press reset button to reset GFCI
after circuit interruption
Dual dimming, tamper-resistant receptacles
15 A 120/125 V CAR-15-DDTR-XX
1
SCR-15-DDTR-XX
2
20 A 120/125 V CAR-20-DDTR-XX
1
SCR-20-DDTR-XX
2
Receptacles for dimming use
• Duplex for dimming both
connected loads
• Projecting nubs prevent standard
plugs from being used
• Requires replacement plug for
dimming table and floor lamps
• Tamper-resistant shutter
mechanism
Half dimming, tamper-resistant receptacles
15 A 120/125 V CAR-15-HDTR-XX
1
SCR-15-HDTR-XX
2
20 A 120/125 V CAR-20-HDTR-XX
1
SCR-20-HDTR-XX
2
Receptacles for half dimming use
• Top half for dimming
• Projecting nub prevents
standard plug from being used
• Requires replacement plug for
dimming table and floor lamps
• Bottom half is a general use
receptacle and will fit standard
duplex plugs
• Tamper-resistant shutter
mechanism
Tamper-resistant, self-testing GFCI receptacles
15 A 125 V, GFCI CAR-15-GFST-XX
1
SCR-15-GFST-XX
2
20 A 125 V, GFCI SCR-20-GFST-XX
2
XX
1
: Gloss color codes
XX
2
: Satin color codes
Wallplates not included. Order separately.
Important notes
•
Receptacles and plugs for dimming use are
UL Listed for use with all Lutron wallbox dimmers
included in this catalog.
•
If there is only one electrical feed to the
receptacle, then the duplex DFDU must be used.
•
If the hot and dimmed hot feeds to the split
duplex HFDU are supplied from different circuits
or split-wired with separate switch-legs, a means
to simultaneously disconnect these circuits
must be provided at the panel board where they
originate (NEC 210.7(C) 2002 Edition). A2-pole
circuit breaker or two single-pole circuit breakers
with an approved handle tie can be used to
accomplish this simultaneous disconnect.
Feed-through dimming panels, which are those
without breakers, are recommended when using
theHFDU.
•
For more information on dimming lamps consult
Lutron Application Note #109, Guide to Dimming
Portable Lamps via Receptacles, at
lutron.com/applicationnotes.
Replacement dimming plugs
120/125 V RP-FDU-10-XX
1
UL/CSA/NOM regulatory approvals.
Replacement plug for dimming
• This plug required for use with
Lutron receptacles for dimming
use—plug will also work in
standard receptacle
• Easily replaces the existing plugs
on lamps
Claro wallplates and accessories Claro wallplates and accessories
14 15
lutron.com/specificationguide | 1.800.523.9466 |
| 1.800.523.9466 | lutron.com/specificationguide
DESIGNER
WALLPLATE
OPENING
DESIGNER
WALLPLATE
OPENING
Volume 1 P/N 367-1746 REV H Volume 1 P/N 367-1746 REV H
XX
1
: Available in White (WH) and Brown (BR)