2.03 SOURCE QUALITY CONTROL
A. All dimming controls shall be 100% function tested
at the time of manufacture. Statistical sampling plan
shall not be acceptable.
PART 3 EXECUTION
3.01 INSTALLATION
A. Contractor shall furnish all devices (dimmers,
accessories, & wallplate kits), labor and other
services necessary for the proper installation of the
devices as indicated on the drawings and specified
herein.
B. Contractor shall be responsible for derating dimmer
capacity if side sections are removed.
C. Contractor shall run separate neutral wires in
120/208 VAC installations.
D. Contractors shall install all backboxes with a
minimum wallbox depth of 2.5 inches.
E. Devices shall be installed utilizing manufacturer's
recommended application, wiring and installation
instructions.
F. Contractor to provide seamless wallplate covers per
specification 2.02 for all devices ganged in a common
box. Contractor shall provide barriers within the box
where required by code.
3.02 FIELD QUALITY CONTROL
A. Twenty-four hours a day, seven days a week, global
customer service and technical hotline available.
B. Supplemental information shall be provided by
manufacturer's Internet site.
b. Receptacles shall be two pole, three wire
ground and rated for 15A at 125VAC. All
receptacles shall be NEMA configuration type
5-15R.
c. Ground-fault interrupter receptacles shall
be Lutron Satin Colors style with two-pole,
three-wire ground and rated 15A at 125VAC
Configuration shall be of the duplex type with
rectangular NEMA WD-6 design. Receptacles
shall have a 5 milliampere ground-fault trip
level with "test" and "reset" buttons.
3. Telephone, Cable, Fiber and BNC Jacks Lutron
Satin Colors Style
a. Contractor shall provide an appropriate barrier
(partition) to isolate jacks from high-voltage
wiring when ganged together. This complies
with NEC Articles 800-3 and 820-13.
b. Telephone jack shall be designed to mate with
standard 4- or 6-conductor modular jacks, and
be compatible with 2, 4, or 6 conductor lines.
Telephone jacks shall meet FCC Part 68,
paragraph F standards to ensure compatibility
with U.S. telephone systems.
c. Cable jacks shall be the coaxial type, designed
for use with standard 75-Ohm cables.
d. Fiber jacks shall meet EIA/TIA-568-B.3
specifications for optical, mechanical and
environmental performance.
e. BNC connectors shall be F/F couplers.
C. Wallplates Lutron Satin Colors Style
1. Wallplates shall be manufactured from durable
polycarbonate plastic with matte finish, and
shall attach to the basic components without
using exposed hardware or screws.
2. Multigang wallplates shall provide a
continuous, seamless cover for up to six-
ganged decorator-style control and accessory
combinations with no exposed hardware or
screws.
3. Multigang wallplates shall include an adapter
plate for proper device alignment and wallplate
attachment.
4. Control, accessory and wallplate profiles shall
not exceed .30 inches from wall surface to
faceplate front surface.
5. To ensure a precise color match between all
plastic parts, color variation of any matte part
shall not exceed a just noticeable level, delta
E of 1, as defined in ASTM E 308-99.
6. Visible parts of dimmers, switches, standard
receptacles, cable jacks or any wallplate shall
exhibit ultraviolet stability when tested as
defined in ASTM D4674-89.