Cut Sheet
product specifications
08.22.17369225l
RadioRA 2 Maestro Local Controls
8
Customer Assistance:
1.844.LUTRON1 (U.S.A. / Canada)www.lutron.com/support
Mixing Lamp Types
Mixing lamp types (using a combination of CFL/LED, Incandescent/Halogen bulbs) and ganging with
other dimmers or electronic switches may reduce maximum wattage as shown in the chart below.
Example: If fins from one side of dimmer are removed and you have two 24 W bulbs installed (total
CFL Wattage = 48 W), you may add up to 300W of incandescent/halogen lighting.
Do not remove outside fins on ends of ganged controls (shaded areas).
Total CFL/LED Wattage
Total Incandescent/Halogen Wattage
A
Not Ganged
B
End of Gang
C
Middle of Gang
Neutral
Connection
RRD-6CL
1,2
0 W + 50 W – 600 W Or 50 W – 500 W Or 50 W – 400 W No
1 W – 25 W + 0 W – 500 W Or 0 W – 400 W Or 0 W – 300 W
26 W – 50 W + 0 W – 400 W Or 0 W – 300 W Or 0 W – 200 W
51 W – 75 W + 0 W – 300 W Or 0 W – 200 W Or 0 W – 100 W
76 W – 100 W + 0 W – 200 W Or 0 W – 100 W Or 0 W – 50 W
101 W – 125 W + 0 W – 100 W Or 0 W – 50 W Or 0 W
126 W – 150 W + 0 W Or 0 W Or 0 W
1
Dimmer Load Type -6CL is designed for use with permanently-installed incandescent, CFL, LED, MLV, or tungsten halogen only. Do not
install dimmers to control receptacles or motor-operated appliances.
2
Do not mix CFL and LED loads with MLV loads.
Compatible Power Boosters and Load Interfaces
Some local controls can be used to control power boosters or load interfaces. Up to three power
boosters or load interfaces can be used with one control. See table below for a list of controls and
compatible power boosters and load interfaces.
Control
Phase Adaptive
Power Modules:
PHPM-PA-120-WH;
PHPM-PA-DV-WH
3-wire Fluorescent
Power Modules:
PHPM-3F-120-WH;
PHPM-3F-DV-WH
Switched Power
Module:
PHPM-SW-DV-WH
0 – 10 V Interface and
Switching Module:
GRX-TVI
RRD-6ND
RRD-10ND
RRD-6NA
RRD-F6AN-DV
1
RRD-8ANS
preferred
1
Only the GRX-TVI is compatible with the RRD-F6AN-DV at 277 V~. All other power modules are 120 V~ only.
A B B B C B