Cut Sheet

®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Vive
PowPak Phase Select Wireless Lighting Control
3691150b 3 03.25.21
Specifications
Regulatory Approvals
• cULus
508 Listed
Complies with the limits for a Class B device, pursuant
to IC and FCC rules
Complies with requirements for use in other spaces
used for environmental air (plenums) per
NEC
® 2014 300.22(C)(3)
Listed in accordance to CAN / ULC S142 standard
method of fire test for heat and visible smoke release
for discrete products
NEMA SSL 7A-2015
• UL
® 924 (RMJS-PNE-DV-EM only)
• NOM
Power
Operating voltage
120 / 277V~ 50 / 60Hz
0 W minimum load
Output Ratings
Output must not be used to control receptacles.
Output must be directly connected to the load.
Output breakers or switches must not be used.
Other Power Specifications
Standby power:
120 / 277 V~ 650 mW typ.
BTU / hour when fully loaded: 23 max.
Inrush current on dimming ballasts or drivers should
not exceed NEMA410 standards for electronic
ballast / driver.
For applications requiring higher wattage ratings, use a
power booster (PHPM-PA-120-WH, PHPM-PA-DV-WH,
or PHPM-PA-277 / DV). Note: The Vive PowPak phase
select dimming module must be set to forward-phase
when used with these interfaces.
For applications requiring 010 V- control, use a 10 V
interface (GRX-TVI).
For applications using Lutron 3-wire fluorescent
dimming ballasts, use the PHPM-3F-120-WH or
PHPM-3F-DV-WH. See https://www.lutron.com/
TechnicalDocumentLibrary/369-355.pdf for more
details.
3