Cut Sheet
Table Of Contents
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Vive
PowPak Phase Select Wireless Lighting Control
3691150b 3 03.25.21
Specifications
Regulatory Approvals
• cULus
508 Listed
• Complies with the limits for a Class B device, pursuant
to IC and FCC rules
• Complies with requirements for use in other spaces
used for environmental air (plenums) per
NEC
® 2014 300.22(C)(3)
• Listed in accordance to CAN / ULC S142 standard
method of fire test for heat and visible smoke release
for discrete products
• NEMA SSL 7A-2015
• UL
® 924 (RMJS-PNE-DV-EM only)
• NOM
Power
• Operating voltage
120 / 277V~ 50 / 60Hz
• 0 W minimum load
Output Ratings
• Output must not be used to control receptacles.
• Output must be directly connected to the load.
• Output breakers or switches must not be used.
Other Power Specifications
• Standby power:
– 120 / 277 V~ 650 mW typ.
• BTU / hour when fully loaded: 23 max.
• Inrush current on dimming ballasts or drivers should
not exceed NEMA410 standards for electronic
ballast / driver.
• For applications requiring higher wattage ratings, use a
power booster (PHPM-PA-120-WH, PHPM-PA-DV-WH,
or PHPM-PA-277 / DV). Note: The Vive PowPak phase
select dimming module must be set to forward-phase
when used with these interfaces.
• For applications requiring 0–10 V- control, use a 10 V
interface (GRX-TVI).
• For applications using Lutron 3-wire fluorescent
dimming ballasts, use the PHPM-3F-120-WH or
PHPM-3F-DV-WH. See https://www.lutron.com/
TechnicalDocumentLibrary/369-355.pdf for more
details.
3