Vive PowPak Relay Module with Softswitch Wireless Lighting Control
369908f 3 03.12.18
Specifications
Regulatory Approvals
• UL
® Listed (U.S.A.)
UL 924 Listed (RMJS-16R-DV-B-EM only)
FCC approved. Complies with the limits for a Class B
device, pursuant to Part 15 of the FCC rules. (U.S.A.)
Complies with requirements for use in other spaces
used for environmental air (plenums) per
NEC
® 2014 300.22(C)(3)
Listed in accordance to CAN/ULC S102.2-2010 with
a Flame Spread Rating of 0 and a Smoke Developed
Classification of 40, with a minimum spacing of 6 ft
(1.83 m) off center
CSA and IC (Canada) (RMJS- only)
COFETEL (Mexico) (RMJS- only)
NOM (Mexico) (RMJS- only)
Power
Operating voltage: 120 / 277 V~ 50/60 Hz
Standby Power Consumption (all models): < 1.0 W
System Communication
Operates using Clear Connect RF Technology for reliable
wireless communication; refer to model number chart on
page 2 for band frequency details
RF range is 30 ft (9 m)
Wireless sensors and controls must be located within
60ft (18 m) line of sight, or 30 ft (9 m), through walls, of
the associated control module. The 60 ft (18 m) range is
not reduced by a ceiling tile obstruction.
Contact Lutron first for applications using foil-backed or
metallic ceiling tiles.
Environment
Ambient operating temperature: 32 °F to 131 °F
(0 °C to 55 °C)
0% to 90% humidity, non-condensing
For indoor use only
All drivers and ballasts used with Vive wireless
controls must comply with the limits for a Class A
device pursuant to Part 15 of the FCC Rules
Load
-16R models: 16 A; -5R models: 5 A;
RMJS-16R models: No minimum load requirements.
Load types include (but are not limited to):
Incandescent, MLV, ELV, Resistive, Inductive,
Magnetic fluorescent, Electronic fluorescent
• Motor rating:
RMJS-16R- and URMJS-16R- models:
1/2 HP (120 V~), 1
1
2 HP (277 V~)
RMJS-5R- and URMJS-5R- models: 1/6 HP (120 V~),
1/3 HP (277 V~)
Softswitch
Patented Softswitch circuit eliminates relay arcing at
mechanical contacts
Extends relay life to an average of 1 million cycles
Output is non-latching
Key Design Features
LED status indicator shows current load status and
provides programming feedback
Power failure memory: If power is interrupted,
connected loads will return to the previous level prior
to interruption
(continued on next page . . .)