Cut Sheet

4
|
Lutron® 24/7 Technical Support—800.523.9466
product specifications
01.21.11
369-225f
Ganging and Derating
Load Type and Capacity
When combining controls in the same wallbox, derating is required. See Load Type and Capacity.
No derating is required for remote dimmers / switches. -8ANS, -RD-277, and -RS-277 have fins that
need to be removed for multigang installations.
Do Not remove outside fins
on end of gang controls
-8ANS, -RD-277, and -RS-277 only:
Middle of gang control
has all fins removed
Each control has
inside fins removed
RadioRA 2 Maestro® Local Controls
Control Load Type Minimum
Load
Not
Ganged
End of
Gang
Middle of
Gang
Neutral
Connection
RRD-6D
1
Incand. 50 W 600 W 500 W 400 W
NO
MLV
2
50 W / VA
450 W /
600 VA
400 W /
500 VA
300 W /
400 VA
RRD-10D
1
Incand. 50 W 1000 W 800 W 650 W
NO
MLV
2
50 W / VA
800 W /
1000 VA
600 W /
800 VA
500 W /
650 VA
RRD-10ND
1, 4
Incand. 10 W 1000 W 800 W 650 W
YES
MLV
2
10 W / VA
800 W /
1000 VA
600 W /
800 VA
500 W /
650 VA
RRD-6NA
1, 4
Incand. /
ELV
5 W 600 W 500 W 400 W
YES
MLV
2
5 W / VA
450 W /
600 VA
400 W /
500 VA
300 W /
400 VA
RRD-F6AN-DV
3, 4, 5
Fluores-
cent / LED
0.05 A 6 A 5 A 3.5 A
YES
1 ballast 60 ballasts 50 ballasts 35 ballasts
RRD-8ANS
4, 6
Lighting 10 W 8 A 6.5 A 5 A
YES
Motor 0.08 A
1/4 HP
5.8 A
1/4 HP
5.8 A
1/6 HP
4.4 A
RRD-8S-DV
6, 7
Lighting 40 W / VA 8 A
8 A (2-gang)
7 A (3-gang)
7 A
NO
Motor 0.4 A
1/10 HP
3 A
Continued on next page...