User Guide

3691183a 2 04.16.21
Lighting Control Systems QS DIN Rail Panel Power Equipment
SPECIFICATION SUBMITTAL
Job Name:
Job Number:
Model Numbers:
Regulatory Approvals
• cULus®
• NOM
• cULus® Listed to be able to add and replace
Lutron DPMs in the field
Power
• Feed-through:
120 / 277 V~ 50 / 60 Hz 20
A max per circuit
• Breaker Panel:
120 / 240 V~ 50 / 60 Hz (single phase 3-wire)
120 / 208 V~ 50 / 60 Hz (three phase 4-wire)
– 15
A or 20
A branch breakers
– 125
A main lugs
Lightning strike protection: Meets ANSI / IEEE standard
C62.41-2000 and IEC 61000-4-5. Can withstand voltage
surges up to 6000V~ and current surges up to 3000A.
• 10 year power failure memory: restores lighting to
levels prior to power interruption.
DIN Modules Available
(maximum of 10)
120 / 277 V~ PRO LED
+
Phase Adaptive
• 120 V~ Switching
• 120 V~ 0–10 V- / Switching
Wiring
Internal: Wired and tested by Lutron.
System communications: NEC® Class 2 wiring
connects panels to control station. Wired sensors must
be wired to QS Sensor Module (QSM).
Line (mains) voltage: only feed and load wiring
required (feed-through panels require feeds for the
module power).
Mounting
• Surface- or recess-mount.
Construction
• 16 AWG (1.5 mm) galvanized sheet metal enclosure
(unpainted).
• 16 AWG (1.5 mm) powder-coated (black) metal cover
with ventilation holes.
Specifications
Environment
• Enclosure: NEMA Type 1, IP-20 protection.
• Mount where ambient temperature is 32 to 104°F
(0to 40ºC). Relative humidity less than 90%,
non-condensing.
• Indoor use only.
Passive cooling (fan is not required)
DPMs generate heat. See device spec sheet for
BTU ratings.
Line Voltage (Mains) Connections
• Feed-through panels
DIN rail-mounted terminal blocks provided for
line-voltage (mains) power to DPMs and to control
equipment power supply.
DIN rail-mounted terminal blocks provided for load
wiring. Use copper wire only.
• Breaker panels
Options available for single phase 3-wire and three
phase 4-wire main input. Main lug connections
provided for line-voltage (mains) power. Power is
distributed to branch circuit breakers, and DPMs
via internal wiring installed by Lutron. Use copper or
aluminum wire (install and wire in accordance with
all local and national codes).
DIN rail-mounted terminal blocks provided for
load wiring. Use copper wire only.
Wire Sizing
• DIN rail-mounted terminal blocks:
Line (mains) and load terminal blocks will accept
one 26 AWG to 10 AWG (0.14 mm
2
to 6.0mm
2
)
wire or two 26 AWG to 16 AWG (0.14mm
2
to
1.5 mm
2
) wires.
• Breaker panel main lugs will accept one 6 AWG to
2 / 0 AWG (16 mm
2
to 70 mm
2
) wire per pole.
continued on next page
2