Cut Sheet

®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
PP and UPP Series -DV, -DV-M, -347H, -SH Power Packs
369544h 3 07.01.16
3 Sensors with Power Pack - Vacancy-Only Solution (PP-DV-M, UPP-DV-M)
1,2
1
Maximum 3 devices (excluding low-voltage momentary switches) can be used with PP-DV-M / UPP-DV-M. Each PP-SH / UPP-SH counts as one
device, each occupancy sensor counts as one device.
2
The PP-DV-M cannot be used for occupancy functionality. It is a vacancy ONLY solution. For occupancy functionality, use the PP-DV.
3
NTRCS-1 (Nova T*® momentary switch) or any low voltage momentary switch rated for at least 24 V-, 100 mA.
Power Pack
(-DV-M)
120-277 V~
50/60 Hz
Lighting
Load
Red (24 V-)
Black (common)
Blue (control)Black
White
Red
Red
Neutral
Ground
Line / Hot
Orange
(manual override)
Low-Voltage
Momentary
Switch
3
Occupancy Sensors
Wiring
3 Sensors with Power Pack (PP-DV, UPP-DV or PP-347H)
1
1
Maximum 3 occupancy sensors can be used with PP-DV / UPP-DV or PP-347H.
2
When lights are manually turned off, switch must be returned back to the on position for occupancy sensors to function as set.
Lighting
Load
120-277 V~ 50/60 Hz (PP-DV / UPP-DV)
347 V~ 60 Hz (PP-347H)
Neutral
Power Pack
(-DV or-347H)
Manual switch OFF
2
(optional – sold
separately)
Red (24 V-)
Blue (control)
Black (common)
Black
White
Red
Red
Line / Hot
Ground
Occupancy Sensors
continued on next page...
3