Cut Sheet
Table Of Contents
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
PP and UPP Series -DV, -DV-M, -347H, -SH Power Packs
369544h 4 07.01.16
Wiring (continued)
Power Pack
(-DV or -347H)
Power Pack
(-DV or -347H)
Switching Multiple Loads with 2 Power Packs (PP-DV / UPP-DV)
Lighting
Load
Lighting
Load
Red (24 V-)
Black
(common)
Occupancy Sensors
Blue (control)
Black
Black
White
White
Red
Red
Red
1
Red
Red
Neutral
Neutral
Ground
Ground
Line / Hot
Lighting
Load
Lighting
Load
Auxiliary
Power Pack
(-SH)
Red
Red
Red (24 V-)
Black (common)
1
Maximum of 3 devices can be used with PP-DV, UPP-DV, or PP-347H. Each PP-SH / UPP-SH counts as one device, each occupancy sensor counts as
one device.
Neutral
Line / Hot
Blue (control)
Black
White
Red
Red
120-277 V~ 50/60 Hz
(PP-DV / UPP-DV);
347 V~ 60 Hz (PP-347H)
Ground
Ground
Occupancy Sensors
Power Pack
(-DV or
-347H)
1
Only 1 Power Pack (PP-DV / UPP-DV) should power the occupancy senors. This 24 V- output is left disconnected.
Switching Multiple Loads with 1 Power Pack and 1 Auxiliary Power Pack
1
120-277 V~ 50/60 Hz
(PP-DV / UPP-DV);
347 V~ 60 Hz (PP-347H)
120-277 V~ 50/60 Hz
(PP-DV / UPP-DV);
347 V~ 60 Hz (PP-347H)
4