Cut Sheet
Table Of Contents
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
PP and UPP Series -DV, -DV-M, -347H, -SH Power Packs
369544h 1 07.01.16
PP and UPP Series Power Packs
PP and UPP 
1
 Series Power Packs provide both the 
24 V- power supply to operate Lutron
® wired occupancy 
sensors, as well as the 16 A line-voltage relay to control the 
load, in one compact housing. The unit can be mounted 
inside a ballast enclosure or inside / outside a junction box. 
 The manual-ON Power Pack (-DV-M) is used to provide 
a vacancy-only solution (not configurable for occupancy 
behavior) when paired with Lutron
® wired occupancy 
sensors. A low-voltage momentary switch should be 
used to manually turn ON the load while the sensor 
automatically shuts the load OFF when unoccupied. 
Pressing the momentary switch can also turn the load OFF. 
 The auxiliary Power Pack (-SH) must be used in 
conjunction with at least one line-voltage Power Pack and 
one Lutron
  wired occupancy sensor to switch additional 
loads.
 Features
• 
High-impact UL94 flammability-rated plastic case 
construction
• Relay: Class B 266°F (130°C) insulating material; silver 
alloy contacts
• Power Pack units (PP-DV / UPP-DV, PP-347H, 
PP-DV-M / UPP-DV-M) power up to 3 total devices. 
PP-SH / UPP-SH counts as 1 device, each occupancy 
sensor counts as 1 device.
• For indoor use only, 32°F to 104°F (0°C to 40°C), 0% to 
90% humidity, non-condensing
(-DV)
(-DV-M [vacancy ONLY]) 
(-347H)
(-SH)
Model Power Input Relay Contact Rating Control Input IEC PELV/ NEC® 
Class 2 Output
PP-DV 
UPP-DV
PP-DV-M (vacancy ONLY)
UPP-DV-M (vacancy ONLY)
120-277 V~
50/60 Hz
6.5 W
• 120-277 V~ 16 A; 
All lighting loads 
2
• 120-277 V~ 1 HP 
Motor Load
24 V- 5mA 24 V- 150 mA 
up to 3 Devices 
3
PP-347H 347 V~ 60 Hz
6.5 W
• 347 V~ 15 A 
Ballast
24 V- 5mA 24 V- 100 mA 
up to 3 Devices 
3
PP-SH 
UPP-SH
24 V- 
(At least one 
line-voltage Power 
Pack must be used)
• 120-277 V~ 16 A; 
All lighting loads 
2
• 120-277 V~ 1 HP 
Motor Load
• 347 V~ 15 A Ballast
24 V- 5mA N/A
1
 “U” denotes BAA compliance
2
  Lighting loads include (but are not limited to): Incandescent, MLV, ELV, Resistive, Inductive
3
 PP-SH / UPP-SH counts as 1 device and each occupancy sensor counts as 1 device
1