Dimmers, Switches, and Accessories Wallbox Controls
369616p 7 10.13.17
Nova T*
When installing more than one dimmer in the same
wallbox,itmaybenecessarytoremovesomeside
sectionspriortowiring(seediagrambelow).Removalof
sidesectionsmayreducemaximumwattage,asshown
inthechartsbelow.
Mixingbulbtypes(usingacombinationofLED/CFLand
incandescent/halogenbulbs)willalsoaffectthe
maximumratings,asshowninthechartsbelow.
Example:Ifonesetofsidesectionsisremovedandyou
haveeight9WLEDbulbsinstalled(TotalLED
Wattage=72W),youmayaddupto500Wof
incandescentorhalogenlightingwiththeC•L
controlor300WwiththeReverse-Phasecontrol.
Derating: Maximum Capacities in Multigang Installations*
Eachcontrolhasinside
sectionsremoved
Middlecontrolhastwoside
sectionsremoved
Donotremoveoutsidesections(shadedareasbelow)
* Formoreinformationonmultiganginstallations,visitwww.lutron.com/en-US/Service-Support/Pages/Technical/InstallationInstructions/Ganging-Derating/
GangingDerating.aspx
(continuedonnextpage…)
Reverse-Phase Electronic Low-Voltage (ELV) Controls
Maximum Allowable Incandescent/Halogen Wattage +
Total LED / CFL Wattage Installed
(Wattage per bulb × number of bulbs)
600 W
500W 400W + 0 W
500W 400W 300 W + 1W–40W
400W 300 W 200W + 41W–80W
300 W 200W 100 W + 81W–120W
200W 100 W 50W + 121W–160W
100 W 50W 0 W + 161W–200W
0 W 0 W 0 W + 201W–250W
• NoderatingisrequiredformultiganginstallationsifonlyLEDbulbsareusedorifnofinsarebroken.
LED
DEL
LFCA
CFL
AFC
Single Units
Fullcapacity.
Nosidesections
removed
End Units
Oneside
section
removed
Middle Units
Two side
sections
removed
Incandescent Controls
600 W 500W 300 W
1000 W 900 W 700 W
1500W 1250W 1000 W
1950W
• NT-2000-XXcontrols(for1950Wcapacity)mustbeganged
withoutremovingsidesections.
C•L Controls
Maximum Allowable Incandescent/Halogen Wattage +
Total LED / CFL Wattage Installed
(Wattage per bulb × number of bulbs)
1000 W 800W 600 W + 0 W
800W 600 W 500W + 1W–40W
600 W 500W 400W + 41W–80W
500W 400W 300 W + 81W–120W
400W 300 W 200W + 121W–160W
300 W 200W 100 W + 161W–200W
0 W 0 W 0 W + 201W–250W
• NoderatingisrequiredformultiganginstallationsifonlyLEDbulbsareusedorifnofinsarebroken.
LED
DEL
LFCA
CFL
AFC
7