Cut Sheet

®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Dimmers, Switches, and Accessories Wallbox Controls
369616p 13 10.13.17
Nova T*
Wiring Diagrams: NTSTV- Controls
• Thetotal0–10V-controlsignalwiringforthiscontrolshouldnotexceed500ft(152.4m).
• Donotusewiresmallerthan20AWG(0.75mm
2
).
• ForClass1installations,0–10V-wiresmustberuninconduitorapprovedcableperNEC®orlocaljurisdiction.
• ForClass2installations,conduitistypicallynotrequired(localcodemayapply).
• Forapplicationwithexcessiveelectricalnoise,0–10V-wiresshouldberuninseparateconduitfromthemains.
Class 1 Installation
Black
White
White
Violet(+)
Violet(+) Violet(+)
Black
Black Black
Gray(–)
Gray(–) Gray(–)
Toadditionalballasts
Line/
Hot
Neutral
010V-
DimmingBallast
orLEDDriver
010V-
DimmingBallast
orLEDDriver
Green
Control
Class1
010V-Control
SignalWires
a
120–277V~
Model:
• NTSTV-DV-XX
Maximum Capacity *
Load 010 V- Sink
8A 30mA
* Whichevercomesfirst.
Class 2 Installation
ON/OFFcontrolusingPowerPack(PP-DVorPP-347H)
Red
b
Black Black
Red
Blue
White
Red
b
Black
Black Black(capped)
White
White
Violet(+)
Violet(+) Violet(+)
Black
Black
Gray(–)
Gray(–) Gray(–)
Toadditionalballasts
Line/
Hot
Neutral
010V-
DimmingBallast
orLEDDriver
010V-
DimmingBallast
orLEDDriver
Green
c
Control
Power
Pack
Class2
010V-Control
SignalWires
a
IECPELV/NEC®Class2wiring:
20AWG(0.75mm
2
)
a
Model:
• NTSTV-DV-XX
Maximum Capacity
Load 010 V- Sink
**
30mA
** SeePP- and UPP-Series Power Packs
specsubmittal,LutronP/N369544
Key
Ground
Wire connector
Wire connector
Typical4-wire
connection
a
DoNOTconnect
tolinevoltage
b
18AWG
(1.0mm
2
)red
wires are
interchangeable.
Connecttoeither
line or load side
c
Greenwiremay
becappedfor
Class2
installationsONLY
¤
P
NP
¤
P
NP
¤
P
NP
¤
P
NP
Notice
• Lutronisnotliablefordamageduetomiswiring0–10V-
controlsignalwireswithlinevoltage.
• DonotrunClass2wiresandlinevoltageconductorstogether
in the same conduit.
13