Multigang Installation
Multiple controls can be installed in a multigang wallbox or a series
of interconnected wallboxes for a clean, consolidated appearance.
Lutron multigang faceplates are available to complete the installation.
Refer to instruction sheet supplied with multigang faceplates for
installation.
For new installations, controls can be ganged without removing side
sections, but, to reduce the size of the multigang installation or to fit
existing wallboxes, inner side sections must be removed. Because
side sections are designed to dissipate heat, removing them derates
the capacity of the control.
Note: When ganging any combination of small and large controls,
place all small controls on one end of the gang and all large controls
on the other. Use the chart below to determine the size and rating of
each control.
*
NT-2000 cannot have side sections removed.
Note: The Wallbox Requirement Charts on this sheet do not apply for the
NT-2000. See the NT-2000 instruction sheet for the appropriate
requirements.
Limited Warranty
(Valid only in U.S.A., Canada, Puerto Rico, and the Caribbean.)
Lutron will, at its option, repair or replace any unit that is defective in materials or manufacture with-
in one year after purchase. For warranty service, return unit to place of purchase or mail to Lutron at
7200 Suter Rd., Coopersburg, PA 18036-1299, postage pre-paid.
THIS WARRANTY IS IN LIEU OF ALL OTHER EXPRESS WARRANTIES, AND THE IMPLIED
WARRANTY OF MERCHANTABILITY IS LIMITED TO ONE YEAR FROM PURCHASE. THIS
WARRANTY DOES NOT COVER THE COST OF INSTALLATION, REMOVAL OR REINSTALLA-
TION, OR DAMAGE RESULTING FROM MISUSE, ABUSE, OR DAMAGE FROM IMPROPER
WIRING OR INSTALLATION. THIS WARRANTY DOES NOT COVER INCIDENTAL OR CONSE-
QUENTIAL DAMAGES. LUTRON’S LIABILITY ON ANY CLAIM FOR DAMAGES ARISING OUT
OF OR IN CONNECTION WITH THE MANUFACTURE, SALE, INSTALLATION, DELIVERY, OR
USE OF THE UNIT SHALL NEVER EXCEED THE PURCHASE PRICE OF THE UNIT.
This warranty gives you specific legal rights, and you may have other rights which vary from
state to state. Some states do not allow the exclusion or limitation of incidental or consequential
damages, or limitation on how long an implied warranty may last, so the above limitations may
not apply to you.
© 2008 Lutron Electronics Co., Inc.
Worldwide Technical and Sales
Assistance
If you have questions concerning the installation or operation of
these products, call the
Lutron Technical Support Center.
Please
provide exact model number when calling.
1.800.523.9466 (U.S.A., Canada, and the Caribbean)
Other Countries call +1.610.282.3800
Fax +1.610.282.6311
Visit our web site at www.lutron.com
Remove inner side sections (shaded)
only.
Do not remove outer side sections.
Side Sections Removed
(Derating Required)
Number of Small Controls
01234
0 0 1 1+1 4 4+1
Number 113568
of Large2467910
Controls 3 6 8 10 11 13
4 9 11 12 14 15
Note: When ganging an even number of small controls with side
sections intact, use gangable 3 in x 2 in (76 mm x 51 mm) wallboxes.
Space an additional wallbox 3/4 in (19 mm) apart from the other
wallboxes. A 3/4 in (19 mm) chase nipple is recommended as a
spacer between wallboxes.
Example: Wallbox arrangement required for ganging 4 small controls
with no side sections removed:
No Side Sections Removed
(Derating Not Required)
Remove inner side sections from controls. Using pliers, bend side
sections up and down until they break off.
Single-gang
wallbox
3/4 in (19 mm) space (use chase nipple
or Lutron P/N “PLUS-ADPTR-3.5”)
Four-gang
wallbox
Wallbox Gang Size Requirement Chart
Wallbox Gang Size Requirement Chart
Control Size and Derating Chart
Control No Sides 1 Side 2 Sides
Model
Size Removed Removed Removed
NT-600 S 600 W 500 W 300 W
NT-1000 S 1000 W 900 W 700 W
NT-1500 L 1500 W 1250 W 1000 W
NT-2000
* L 1950 W
NTLV-600 S 600 VA/ 450 W 500 VA/ 400 W 300 VA / 200 W
NTLV-600-277 S 600 VA/ 450 W 500 VA/ 400 W 300 VA/ 200 W
NTLV-1000 S 1000 VA/ 800 W 900 VA/ 700 W 700 VA/ 550 W
NTLV-1000-277 S 1000 VA/ 200 W 900 VA/ 1000 W 700 VA/ 800 W
NTLV-1500 L 1500 VA / 1200 W 1250 VA/ 1000 W 1000 VA/ 800 W
NT-603P S 600 W 500 W 300 W
NT-1003P S 1000 W 900 W 700 W
NT-1503P L 1500 W 1250 W 1000 W
NTLV-603P S 600 VA/ 450W 500 VA/ 400W 300 VA/ 200W
NTLV-1003P S 1000 VA/ 800W 900 VA / 200W 700 VA / 550W
NTLV-1503P L 1500 VA / 1200W 1250 VA/ 1000W 1000 VA/ 800W
NTELV-300 S 300 W 300 W 250 W
NTELV-600 S 600 W 500 W 400 W
NTFS-6E S 6 A 4.2 A 2.5 A
NTFS-12E L 12 A 10 A 8.3 A
NTFSQ S 1.5 A 1.5 A 1.5 A
NTF-10 S 16 A 16 A 16 A
NTF-10-277 S 8 A 8 A 8 A
NTFTU-5A S 5 A 4 A 3.3 A
NT-1PS S 20 A 20 A 20 A
NT-3PS S 20 A 20 A 20 A
NT-4PS S 20 A 20 A 20 A
Number of Small Controls
0123456
00123456
Number 11345678
of Large 235678910
Controls 35789101112
4 7 9 10 11 12 13 14