Cut Sheet

13
c. Eight-conductor telephone jacks shall be Category 5 Voice
and Data rated. They shall be FCC Part 68, Sub-part F
compliant.
d. Cable TV jacks shall be the coaxial type, designed for use
with standard 75-Ohm cables.
e. Category 5 voice, data, or cable configurations shall be
available in single gang, up to three functions per gang.
C. Wallplates Lutron Nova T
a Style
1. Wallplates shall be manufactured from durable polycarbonate
plastic with matte finish, and shall attach to the basic
components without using exposed hardware or screws.
2. Multigang wallplates shall provide a continuous, seamless cover
for control and/or accessory combinations with no exposed
hardware or screws. Custom wallplate configurations shall be
available.
3. Multigang wallplates shall include snap in auto-align adapter
plate for proper device alignment and wallplate attachment.
4. Control, accessory and wallplate profiles shall not exceed
.30 inches from wall surface to faceplate front surface.
5. To ensure a precise color match between all plastic parts, color
variation of any gloss finish control or wallplate shall not exceed
delta E of 1, CIE L*a*b* color units, as defined in ASTM E 308-99.
6. Visible parts of dimmers, switches, standard receptacles, cable
jacks or any wallplate shall exhibit ultraviolet stability when
tested with multiple actinic light sources as defined in ASTM
D4674-89.
2.03 S
OURCE
Q
UALITY
C
ONTROL
A. All dimming controls shall be 100% function tested at the time of
manufacture. Statistical sampling plan shall not be acceptable.
PART 3 – EXECUTION
3.01 I
NSTALLATION
A. Contractor shall furnish all devices (dimmers, accessories, &
wallplate kits), labor and other services necessary for the proper
installation of the devices as indicated on the drawings and
specified herein.
B. Contractor shall be responsible for derating dimmer capacity if side
sections are removed.
C. Contractor shall run separate neutral wires in 120/208 VAC
installations.
D. Devices shall be installed utilizing manufacturer's recommended
application, wiring and installation instructions.
E. Contractor to provide seamless wallplate covers per specification
2.02 for all devices ganged in a common box. Contractor shall
provide barriers within the box where required by code.
3.02 F
IELD
Q
UALITY
C
ONTROL
A. Twenty-four hours a day, seven days a week, global customer
service and technical hotline available.
B. Supplemental information shall be provided by manufacturers
Internet site.
Lutron Electronics Co., Inc.
7200 Suter Road • Coopersburg, PA 18036 U.S.A.
Made and printed in U.S.A. 12/2004 ©2004