Installation Guide

Package Contents:
Important Notes
Please Read Before Installation
IMPORTANT: For best performance use with Lutron Tu-Wire line-
voltage control electronic fluorescent dimming ballasts. For other
applications please contact Lutron Technical Support. Note: For
proper dimming performance, lamps must be operated at full
intensity for 100 hours prior to dimming.
Caution: To avoid overheating and possible damage to other
equipment, do not install to control receptacles, motor-operat-
ed appliances, or transformer supplied appliances.
Short Circuit Check: Check new installation for short circuits
prior to installation of control by using a single pole switch and
connecting the appropriate terminals to the hot wire and the lamp
with power OFF. Turn power on. If lights do not work, or breaker
trips, a short is present. Correct the wiring and check circuit again.
Install control only when short is no longer present.
Wire Connectors: Wire connectors provided can be used to join
one 10-, 12-, 14-, 16-, or 18-gauge wire with one or two 12- or 14-
gauge wires. Use them with copper wire only.
Wallbox and Location: A single-gang wallbox (3" high x 2" wide
x 2 1/2" deep (76 mm high x 51 mm wide x 64 mm deep)) will
service all individual Nova controls. These controls are designed to
operate in ambient temperatures from 0 °C to 40 °C (32 °F to 104
°F). Allow a minimum of 4 1/2" (114 mm) free space above and
below the controls for proper heat dissipation.
Multigang Installations: A multigang wallplate is available to
simplify and improve the appearance of your installation. A multi-
gang mounting frame is provided with each standard multigang
wallplate to ensure proper alignment of the controls, easy applica-
tion of the wallplate, and a flat surface for the installation. Refer to
instruction sheet supplied with multigang wallplates.
Cleaning Instructions: To clean, wipe with a clean damp cloth.
DO NOT use any chemical cleaning solutions.
Offset Mounting Holes
Center Mounting Holes
Figure A. Front View - Single Unit Installation
Installation Instructions
Please Leave for Occupant
Tu-Wire® Fluorescent Controls
NFTU-5A
120 V , 60 Hz, 5 A
Single Unit Installation
1. Turn power OFF at fusebox or circuit breaker. Wiring with
power on can result in personal injury. Damage to product caused
by wiring with power on voids warranty.
2. Remove wallplate from control to prevent damage and to
access mounting holes. Pull out at top and bottom edges, plate
will snap off.
3. Strip insulation from control wires and from wires to which
control is to be connected as follows:
1/2" (13 mm) for 10, 12, and 14 gauge supply wire
5/8" (16 mm) for 16 and 18 gauge control wire
4. Using the wire connectors provided, make connections follow-
ing the appropriate wiring diagrams for your control.
Note: If a bare copper or green ground connection is not available
in the wallbox, contact a licensed electrician for installation.
5. Push wires into wallbox, allowing room for control backbox to
be inserted.
6. Mount control to wallbox using 2 screws provided and center
mounting holes. Unit must be mounted vertically. See Figure A.
1/2" (13 mm) or
5/8" (16 mm)
Figure B. Snap on Wallplate
Press Wallplate Until Tabs Snap In
Wallplate
Tabs
7. Snap wallplate on. See Figure B.
Slider
Mounting
Screws
Control
Wallplate
Wire
Connectors