Installation Guide

1
Pre-Installation
1. Determine the number of controls to be ganged in the same
wallbox. If installing a single control in a wallbox, continue to the
"Single Unit Installation" section on page 3.
2. If more than one control is being ganged in the same
wallbox, side sections can be removed to fi t in existing
wallboxes. When controlling magnetic ballasts, breaking side
sections off the control will reduce the maximum number of
lamps per control. Use the following charts to determine the
maximum number of lamps per control.
Installation Instructions
Please Leave for Occupant
Fluorescent Controls
120 V~ 60 Hz: NF-10 16 A
NF-20 10.2 A
NF-30 15.3 A
277 V~ 60 Hz: NF-10-277 8 A
NF-20-277 4.5 A
Package Contents and Part Identifi cation
Control
Mounting
Screws
Slider
Wallplate
Wire
Connectors
Control
Shaft
Screwdriver
Important Notes
Please Read Before Installing
Wallbox and Location: A single-gang wallbox (3 in high x 2 in
wide x 2.5 in deep) 76 mm high x 51 mm wide x 64 mm deep))
will service all individual Nova controls. These controls are
designed to operate in ambient temperatures from 0
o
C (32
o
F) to
40
o
C (104
o
F). Allow a minimum space of 4.5 in (114 mm) above
and below the control for proper heat dissipation.
Short Circuit Check: Check new installation for short circuits
prior to installing control. With POWER OFF, connect incoming
neutral to the white wire, and the hot wire to both ballast input
wires (black wire with brown wire or yellow/blue wire or orange
wire, depending on ballast used). Turn power ON. If lights do not
work, or breaker trips, a short is present. Correct the wiring and
check circuit again. Install control only when short is no longer
present. This check should be done by a qualifi ed electrician.
Sockets: Use only with rapid start lamp sockets. Lamp
disconnect sockets may be required for use with certain
manufacturer's ballasts. This is in order to meet U.L. and NEC
®
regulations and maintains personal safety standards. Lutron
does not require lamp disconnect sockets with their ballasts.
Refer to the manufacturer's ballast label for this information.
Lamps: Use only rapid start fl uorescent lamps. Energy Saver
Lamps may NOT be used with this control. With magnetic
ballasts only, do not mix different wattage lamps in the same
circuit. NOTE: For proper dimming performance lamps must be
operated at full intensity for 100 hours prior to dimming.
Ballasts: Use ONLY dimming ballasts listed on chart in step 2 of
Pre-Installation. With magnetic ballasts only, do not mix 1 and
2 lamp ballasts in any one control circuit. Do not mix ballasts
manufactured by more than one company. Using single lamp
ballasts will produce the most consistent low end dimming level.
Multi-phased Applications (120/208-3 Phase): In multi-phased
applications use a separate neutral for each phase containing a
control. Contact the Lutron Technical Support Center toll-free
for Application Note #17, "Common Neutral Interaction".
Clean control with a soft damp cloth only. DO not use any
chemical cleaners.
** Only NF-10 may be used with Lutron Ballasts. Total Amps are determined by
adding all ballast line currents as indicated on ballast label.
Lutron
Hi-lume
®
16 A
Eco-10
Electronic
Ballasts
NF-10**
Number of Side Sections Removed
None One Two
NF-10 NF-20 NF-30 NF-10 NF-20 NF-30 NF-10 NF-20 NF-30
Universal
550LTCP
12 24 36 9 22 34 6 19 31
502ATCP
* 12 24 36 9 20 32 4 18 28
Advance
DIM 140H 10 20 30 7 18 27 4 15 25
DIM 240H* 10 20 30 6 18 26 4 14 24
Valmont
8G5001W 12 24 36 9 22 34 6 19 31
8G5007W* 12 24 36 9 20 32 4 18 28
can be used with 30W lamps
* 2 lamp ballast
NF-10 controls when used with
Lutron electronic dimming ballasts
do not require derating when side
sections are removed.
Figure A: Derating Ballast Chart
120 V~ Applications
277 V~ Applications
Lutron
Hi-lume
®
8 A
Eco-10
** Only NF-10-277 may be used with Lutron Ballasts. Total Amps are determined by
adding all ballast line currents as indicated on ballast label.
Magnetic
Ballasts
Number of Side Sections Removed
None One Two
NF-10-277 NF-20-277 NF-10-277 NF-20-277 NF-10-277 NF-20-277
Magnetek
Universal
679LTCP 12 24 11 21 10 20
678LTCP 12 24 10 20 10 20
Controls
Ballasts
Controls
Ballasts
NF-10-277 controls when used
with Lutron electronic dimming
ballasts do not require derating
when side sections are removed.
Magnetic
Ballasts
Electronic
Ballasts
NF-10-277**
Units listed are maximum number of LAMPS per control
Units listed are maximum number of LAMPS per control