Installation Guide
Installation Instructions
Please Leave for Occupant
Incandescent Preset Dimmers
N-603P, N-1003P, N-1503P, N-2003P
120 V , 60 Hz
Installation:
1.
TURN OFF POWER. Control may only be installed when
power is turned off. Remove fuse or turn circuit breaker off.
2. Remove wallplate from dimmer to prevent damage and to
access mounting holes. Pull out at top and bottom edges,
plate will snap off.
3. Strip wallbox wires to the following lengths:
• 1/2" (13 mm) for 10, 12, and 14 gauge wire
• 5/8" (16 mm) for 16 and 18 gauge wire
4. Use wire connectors supplied to make connections as shown
in diagram.
5. To wire in a single pole application:
• Connect the green ground wire on the dimmer to the green
or bare copper ground wire in the wallbox.
• Connect the black wire on the dimmer to the live wire coming
from the fusebox or circuit breaker.
• Connect one red wire on the dimmer to the wire going to the
light.
• Cap off the remaining red wire on the dimmer with a wire
connector. The control will function properly if either red wire is
used. See Figure 1.
IMPORTANT NOTES:
Please read before installing.
• To avoid overheating and possible damage to the other
equipment, do not use to control a receptacle, a fluorescent
lighting fixture, a motor-operated appliance, or a transformer-
supplied appliance.
• For incandescent lamps operating on 120 V , 60 Hz only.
• Allow a minimum space of 4-1/2" (114 mm) above and below
the dimmers for proper heat dissipation.
• Check new installation for shorts prior to installation of
dimmer by using a standard switch and connecting
appropriate wires to hot line and lamp with POWER OFF.
Turn power ON. If lights do not work or breaker trips, a short
is present. Correct the wiring and check circuit again. Install
dimmer when short is no longer present.
• If a green or bare copper ground connection is not available
in the wallbox, contact a licensed electrician.
• Turn POWER OFF when installing dimmer. Wiring with
power on may result in personal injury or damage to this
product which will void the warranty.
• For use where ambient temperatures range from 0 °C -
40 °C (32 °F - 104 °F)
• Dimmers must be mounted vertically.
• Clean dimmer with a soft damp cloth only. Do not use
any chemical cleaners.
1/2" (13 mm) or
5/8" (16 mm)
Figure 1. Single Pole Wiring
Neutral
Light
Red
Red
Black
Live
120 V
60 Hz
Ground