Cut Sheet
Table Of Contents
®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Maestro® Occupancy/Vacancy Sensor with C•L Dimmer Sensor
369748a 3 01.11.13
Control Voltage Load Type
1
Minimum
Load
Maximum Load Neutral
Connection
Required
Not Ganged End of
Gang
Middle of
Gang
MSCL-OP153M
MSCL-VP153M
120 V~
Incandescent,
halogen,
CFL, LED
2
1 bulb, or
as noted
on
approved
bulb list
3
600 W incan/
halogen
or
150 W CFL/
LED
500 W incan/
halogen
or
150 W CFL/
LED
400 W incan/
halogen
or
150 W CFL/
LED
NO
Load Type and Capacity
1
Dimmer Load Type: designed for use with permanently installed lighting fixtures only. Do not install dimmers to control receptacles or motor-operated appliances.
2
For mixed load types, see Mixed Load Type and Capacity section.
3
For a complete list of approved Dimmable CFLs and LEDs, please visit www.lutron.com/dimcflled. For questions call: 1.800.523.9466.
Additional Information
• For MaestroR Occupancy sensing switch models, please see LutronR P/N 369666 at www.lutron.com.
• Lutron Technical Hotline: 1.800.523.9466.
Mixed Load Type and Capacity
Total W CFL/LED
+
A B C
0 W 10 W – 600 W 10 W – 500 W 10 W – 400 W
1 W – 25 W 0 W – 500 W 0 W – 400 W 0 W – 300 W
26 W – 50 W 0 W – 400 W 0 W – 300 W 0 W – 200 W
51 W – 75 W 0 W – 300 W 0 W – 200 W 0 W – 100 W
76 W – 100 W 0 W – 200 W 0 W – 100 W 0 W – 50 W
101 W – 125 W 0 W – 100 W 0 W – 50 W 0 W
126 W – 150 W 0 W 0 W 0 W
Derating Chart
Placing dimmers adjacent
to mechanical switches
does not require derating.
A B CB B B
INC / HAL
A B C
LED
DEL
LFCA
CFL
AFC
LFCA
CFL
AFC
LED
DEL
Incandescent / Halogen : Total Wattage
Determine allowable wattage (W) of
dimmer by following the steps below.
If multiple dimmers are to be installed
adjacently in the same wallbox, derating
is required.
Derating Chart
1. Determine total wattage of CFL/LED
bulbs installed for dimmer control.
2. Determine total wattage of Incandescent/
Halogen bulbs to be controlled by the
dimmer.
3. Use the Derating Chart to determine
if your total wattages are within the
allowable range of your configuration.
4. Derating Procedure (if necessary)
If multiple dimmers are installed
adjacently in the same wallbox, heat fins
MUST be removed between adjacent
dimmers. This will permanently derate
the dimmer, reducing its total allowable
Incandescent/Halogen wattage.
Example
If heat fins from one side of dimmer are removed (see
B
in chart) and you have two
24 W CFL bulbs installed (Total CFL Wattage = 48 W), you may add up to 300W of
Incandescent/Halogen lighting.
Heat Fins
3