Cut Sheet

RF Local Controls
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Maestro Wireless Designer-style: Maestro
369143o 12 01.06.17
1
A LUT-MLC ensures proper function when low-wattage fluorescent, CFL, or LED loads are used. Install the LUT-MLC inside a load fixture or in a separate
J-box within the circuit.
2
When using controls in single-location installations, tighten the blue terminal without any wires attached. Do not connect the blue terminal to any other wiring
or to ground.
3
Up to nine Maestro Companion Switches may be connected to the Maestro Wireless Switch. Total blue terminal wire length may be up to 250 ft (76 m).
4
Requires MA-AS / MSC-AS for 120 V~ applications, and MA-AS-277 / MSC-AS-277 for 277 V~ applications.
Single-Location Switch Installation with LUT-MLC
1
MRF2-8S-DV
Switch
Load LUT-MLC
1
Brass
Black
Hot/Live
Green
Optional
*
Blue
2
Ground
Neutral
120 V~ 60 Hz
or
277 V~ 60 Hz
Multi-Location Switch Installation with LUT-MLC
1,2,3
MRF2-8S-DV with MA-AS / MA-AS-277 or MSC-AS / MSC-AS-277
4
Companion Switch Companion Switch Switch
BrassBrassBrass
BlackBlackBlack
Hot/Live
GreenGreenGreen
BlueBlueBlue
GroundGroundGround
Neutral
120 V~ 60 Hz
or
277 V~ 60 Hz
Load LUT-MLC
1
Optional
*
Wiring Diagrams (continued)
* Optional Procedure:
Using LUT-MLC with MRF2-8S-DV-XX
Install MRF2-8S-DV-XX first without LUT-MLC to
see if required. Check for problems with load.
Problems can occur when low-wattage loads are
used (< 40 W).
Watch for flickering loads when dimmer is in
electronic OFF state.
If required, LUT-MLC can be installed between
switched hot and neutral in wallbox if neutral is
present, or in any fixture on the switched circuit.
12