Specification Sheet

®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Dual-Circuit Switch with Occupancy/Partial-On Sensor
369758c 7 01.02.14
Maestro® Sensor
Wiring
Single-Line Wiring
120–277 V~
Neutral
Black Black
Load 1
Load 2
Bare copper Green
Striped Striped
Note: Ground connection required for functionality
Two-Line Wiring*
Line 1: 120–277 V~
Neutral 2
Black Black
Load 1
Load 2
Bare copper Green
Line 2: 120–277 V~
Neutral 1
Striped Striped
Note: Ground connection required for functionality
*
Wiring must comply with 2011 NEC code 210.7 for wiring Multiple Branch Circuits: Where two or more branch circuits supply devices or equipment on the
same yoke, a means to simultaneously disconnect the ungrounded conductors supplying those devices shall be provided at the point at which the branch
circuits originate.
7