Specification Sheet

®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Dual-Circuit Switch with Occupancy/Partial-On Sensor
369758c 5 01.02.14
Maestro® Sensor
Horizontal Beam Diagram
(for reference only)
5 ft
(1.5 m)
5 ft
(1.5 m)
0
10 ft
(3 m)
10 ft
(3 m)
15 ft
(4.5 m)
15 ft
(4.5 m)
20 ft
(6 m)
20 ft
(6 m)
25 ft
( 7.5 m)
25 ft
( 7.5 m)
30 ft
(9 m)
30 ft
(9 m)
Vertical Beam Diagram
5 ft
(1.5 m)
10 ft
(3 m)
15 ft
(4.5 m)
20 ft
(6 m)
25 ft
( 7.5 m)
30 ft
(9 m)
4 ft
(1.2 m)
0
Occupancy Sensing Switch Placement and Operation
The ability of the Occupancy Sensing Switch to detect motion requires line-of-sight of room occupants. The
Occupancy Sensing Switch must have an unobstructed view of the room.
Hot objects and moving air currents can affect the performance of the Occupancy Sensing Switch. Switch
performs best when located 4 ft (1.2 m) or more away from hot objects or moving air currents.
The performance of the Occupancy Sensing Switch depends on a temperature differential between the ambient
room temperature and that of room occupants. Warmer rooms may reduce the ability of the Occupancy Sensing
Switch to detect occupants.
Definitions
Major motion: movement of a person entering or passing through an area.
Minor motion: movement of a person occupying an area and engaging in small activities (e.g., reaching for a
telephone, turning the pages of a book, opening a file folder, picking up a coffee cup).
0 10 ft
(3 m)
15 ft
(4.5 m)
20 ft
(6 m)
25 ft
( 7.5 m)
30 ft
(9 m)
5 ft
(1.5 m)
5 ft
(1.5 m)
0
10 ft
(3 m)
10 ft
(3 m)
15 ft
(4.5 m)
15 ft
(4.5 m)
5 ft
(1.5 m)
NEMA WD7 Coverage
Major motion coverage: 900 ft
2
(81 m
2
)
Minor motion coverage: 400 ft
2
(36 m
2
)
Test Room Dimensions: 37 ft x 38 ft (11.28 m x 11.6 m)
Test Floor Surface Material: Carpet
Sensor Coverage Angle: 180°
Major motion coverage: Initial trigger motion detection
Minor motion coverage: Maintained motion detection