Installation Sheet
Important Notes
Please read before installing.
1. Device will not function if it is not
grounded. Both bare and green ground
wires are required to connect to ground.
If no ground is available, consult an
electrician.
2. Device will not function if Black wires
(Circuit 1/Line 1) are not wired.
3. This product is rated to control 6 A per
circuit. Circuits may NOT be wired in
parallel to control loads greater than 6 A.
4. CAUTION: Risk of Electric Shock —
More than one disconnect switch may be
required to de-energize the equipment
before installing the unit, rewiring, or
replacing bulbs.
5. When power is applied, the dual-
circuit sensing switch can be manually
turned on or off after 60 seconds and
will automatically control the load after
2minutes.
6. The dual-circuit sensing switch requires
an unobstructed view of the room and
line-of-sight to detect motion.
7. Hot objects or moving air currents can
affect the performance of the dual-circuit
sensing switch and may cause the sensor
to turn on unexpectedly or maintain its
current state longer than desired.
8. CAUTION: To reduce the risk of
overheating and possible damage to
other equipment, DO NOT use to control
receptacles.
9. Install in accordance with all national and
local electrical codes.
10. For indoor use only. Operate between 32°F
and 104°F (0 °C and 40 °C).
11. DO NOT exceed 20 devices at 120V~ or
7 devices at 277 V~ on a single branch
circuit.
12. Clean with a soft damp cloth only. DONOT
use any chemical cleaners.
Wiring
NOTE: Leave wallplate off if custom settings are desired. See Custom Settings instructions on reverse side.
1
Device will not function if Black wires (Circuit 1/ Line 1) are not wired.
2
Device will not function if it is not grounded.
Black
1
GreenBare
Black-Orange
Neutral
Load 1
Load 2
120-277 V~
Black
Black-Orange
Ground
2
A
. Single-Line Wiring
B
. Two-Line Wiring
Black
1
Green
Ground
2
Bare
Black-Orange
Neutral 2
Line 1
Load 1
Load 2
Line 2
120-277 V~
Neutral 1
Black
Black-Orange
120-277 V~
2
Connect dual-circuit sensing switch
WARNING! Shock Hazard. May result in serious injury or death. Turn power OFF at circuit
breaker(s) before installing the unit, rewiring, or replacing bulbs.
1
Turn power OFF
A
.
I
I
I
O
O
O
Single-Line
I
I
I
O
O
O
B
.
Two-Line*
®
Dual-Circuit Occupancy
Sensing Switch
P/N 032444 Rev. A 11/2013
MS-OPS6-DDV
Occupancy
MS-PPS6-DDV
Partial-ON only
Lutron Electronics Co., Inc.
7200 Suter Road
Coopersburg, PA 18036-1299 U.S.A.
www.lutron.com
®
Single-pole only
Two circuits, each rated at:
Circuit1
Tap Button
Top
programming
button
Bottom
programming
button
Circuit2
Tap Button
Limited Warranty (Valid only in U.S.A., Canada, Puerto Rico, and
the Caribbean). Lutron will, at its option, repair or replace any unit
that is defective in materials or manufacture within five years after
purchase. For warranty service, return unit to place of purchase or
mail to Lutron at 7200 Suter Rd., Coopersburg, PA 18036-1299,
postage pre-paid. This warranty is in lieu of all other express
warranties, and the implied warranty of merchantability is limited
to FIVE years from purchase. This warranty does not cover the cost
of installation, removal or reinstallation, or damage resulting from
misuse, abuse, or damage from improper wiring or installation.
This warranty does not cover incidental or consequential damages.
Lutron’s liability on any claim for damages arising out of or in
connection with the manufacture, sale, installation, delivery,
or use of the unit shall never exceed the purchase price of the
unit. This warranty gives you specific legal rights, and you may
have other rights which vary from state to state. Some states do
not allow the exclusion or limitation of incidental or consequential
damages, or limitation on how long an implied warranty may last,
so the above limitations may not apply to you.
Lutron and Maestro are registered trademarks of Lutron
Electronics Co., Inc.
© 2013 Lutron Electronics Co., Inc.
Major motion coverage:
30 ft × 30 ft (9 m × 9 m) [900 ft
2
(81 m
2
)]
Minor motion coverage:
20 ft × 20 ft (6 m × 6 m) [400ft
2
(36m
2
)]
* Wiring must comply with NEC code for wiring Multiple Branch Circuits: Where two or more branch circuits
supply devices or equipment on the same yoke, a means to simultaneously disconnect the ungrounded
conductors supplying those devices shall be provided at the point at which the branch circuits originate.
OR
3
Turn Power ON
OR
I
I
I
O
O
O
A
.
I
I
I
O
O
O
B
.
4
Wait for 60 seconds before manual switching
• The sensing switch will not manually control the load for 60 seconds.
5
Wait for an additional 60 seconds for automatic switching
• Once power has been restored, the sensing switch will not
automatically control the load for the first 2 minutes.
60 s
60 s
Lighting
(incandescent, halogen, CFL, LED, ELV, MLV,
electronic fluorescent, magnetic fluorescent)
120-277 V~ 50 / 60 Hz 6 A
Fan
120 V~ 50 / 60 Hz 4.4 A 1/6 HP
Combined lighting and fan load
120 V~ 50 / 60 Hz 4.4 A
English