Specification Sheet

®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Dual-Circuit Switch with Occupancy/Partial-On Sensor
369758c 1 01.02.14
Maestro® Sensor
MS-OPS6-DDV-XX
1
(Occupancy model
2
)
UMS-OPS6-DDV-XX
1
(Occupancy model
2, 3
)
MS-PPS6-DDV-XX
1
(Partial-ON only model
2
)
UMS-PPS6-DDV-XX
1
(Partial-ON only model
2, 3
)
1
“XX” in the model number represents color/finish code. See Colors and
Finishes at end of document.
2
Wallplate not included.
3
BAA-compliant model number.
Maestro® Dual-Circuit
Occupancy Sensing Switch
The Lutron® Maestro® Dual-Circuit Occupancy Sensing
Switch combines two switches with an in-wall, passive
infrared (PIR) occupancy or partial-on sensor. The
sensor is intended for either:
Control of two circuits
Bi-level control of two circuits, as required by certain
energy codes (e.g., ASHRAE)
Features
Passive infrared sensor with exclusive Lutron
® XCTTM
Technology for minor motion detection
180° sensor field-of-view
Tamper-resistant PIR lens
Up to 30 ft x 30 ft (9 m x 9 m) [900 ft
2
(81 m
2
)] major
motion coverage and 20 ft x 20 ft (6 m x 6 m) [400 ft
2
(36 m
2
)] minor motion coverage
Smart Ambient Light Detection (ALD) mode uses
adaptive algorithm: Sensor learns the user’s preferred
light level over time
Occupancy version can be set to Auto-ON / Auto-OFF
or Manual-ON / Auto-OFF
Meets Title 24 / Title 20 requirements for multi-level
lighting. Partial-ON only (PPS6-DDV) version available
to meet Title 24 / Title 20 requirements for Partial-ON
sensors
Adjustable timeout for each circuit (1, 5, 15, or 30
minutes)
Sensitivity adjustment (High/Low)
Switches all lighting loads: incandescent, halogen,
ELV, MLV, CFL, LED, magnetic fluorescent, electronic
fluorescent
Switches fan loads at 120 V~
Single-pole only
1

Summary of content (8 pages)