Cut Sheet

®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Dual Technology Occupancy Sensor Switch
369773c 3 04.09.14
Maestro® Sensor
Custom Settings
Default settings shown in bold
- Timeout
30 min
15 min
5 min
1 min
Mode - Sensor Modes
Lights automatically turn off in all sensor modes
Occ -Occupancy mode (No ALD)
1,2,3
Lrn - Occupancy with learning ALD mode
Fixd - Occupancy with fixed ALD mode
Vac - Vacancy mode (No ALD)
2,3
1 MS-A102-XX, MS-B102-XX default is Occ
2 MS-A102-V-XX, MS-B102-V-XX is locked as Vac
3 MS-A202-XX, MS-B202-XX defaults are: Circuit 1 - Occ, Circuit 2 - Vac
- Ultrasonic Sensitivity
• High
Med
• Low
• Off
- Passive Infrared Sensitivity
• High
• Med
• Low
• Min
Additional Settings
Fixed ALD Light Level
• Hi
• Med
Low *
• Min
*
“Low” is the default setting for any sensor that is
set by the user to: Occupancy with fixed ALD mode
Off-While-Occupied
• Enabled
• Disabled
Walk-Thru Mode
• Enabled
• Disabled
Custom Settings - Details
Ambient Light Detection (ALD) mode
Lights turn on only when natural light in the room is
below the set threshold.
Learning: The ambient light threshold adjusts to
the user’s preference via manual interaction with
the sensor switch.
Fixed: Choose a fixed ALD light level from four
pre-set options:
High, Medium, Low, and Minimum
Manual Off-While-Occupied Options
ENABLED (default setting)
When the sensor switch is manually turned off,
the sensor switch will not turn the lights back on
automatically while the room is occupied.
Once the room is vacated, the Auto-On feature
returns to normal operation after the timeout
period has expired.
This may be the preference in conference rooms
or classrooms while viewing presentations. This
feature requires motions to keep the lights off.
DISABLED
When the sensor switch is manually turned off,
the Auto-On feature will return to normal operation
after 25 seconds.
This may be the preference in a restroom if the
user always wants the lights to turn on upon
entering and the lights to turn off when the room
is vacant.
Walk-Thru Mode
ENABLED
1
If motion is not detected within 3 minutes after
initial occupancy, the lights will turn off after
3 minutes, instead of the current timeout.
This setting may be the preference in commercial
applications where personnel may briefly trigger
sensors during non-working hours.
DISABLED
(default setting)
When motion is detected, the lights will ALWAYS
remain on for the entire timeout duration,
regardless of the duration of occupancy detection.
1
1 minute timeout would be overridden if walk-thru mode is also ENABLED