Installation Guide
Select Custom Settings
®
Press and hold the same programming button until the
IL
goes solid to lock your selection
(about 3 seconds).
3
Technical Assistance: www.lutron.com | U.S.A., Canada, Caribbean: 1.800.523.9466 | Mexico: +1.888.235.2910 | Others: +1.610.282.3800
Change Settings
Tap the same programming button to cycle to your desired setting.
2
1
Using ONLY the or
M
to enter programming mode will set BOTH circuits to the new setting.
Holding or
M
and
T
1
or
T
2
simultaneously will program settings for that specific circuit.
2
Circuit 1 Default: Occupancy; Circuit 2 Default: Vacancy.
3
ALD (Ambient Light Detection) Learn mode will turn lights on only if natural light in room is low. If
switch turns on when there is enough natural light, or if switch does not turn on when there is not
enough natural light, press the tap button within 5 seconds of entering the room. Over time, the
switch will learn your preferred setting. If both circuits are set to Occ with Learning ALD mode, they
will learn the SAME threshold.
4
ALD (Ambient Light Detection) Fixed mode will turn the lights on only if natural light in room is low. The
light level at which lights will automatically turn on (or stay off) can be adjusted through the “Set ALD
Fixed Level” setting in “Additional Settings” section.
Additional Settings
Note: Additional product information, including “Circuit Swapping”, and other programming
options and wiring diagrams are available at www.lutron.com/DTMaestroInstall
Test Mode
Test Mode is a short timeout (less than 15 seconds) that will test the coverage of the sensor at the
current settings.
To enable Test Mode:
1. Wait 2 minutes after initial power up.
2. Press and hold either
T
1
or
T
2
until the PIR lens flashes (about 7 seconds).
3. The device will exit Test Mode automatically after 5 minutes of inactivity, or when any button is
pressed.
Note: An amber LED flashes to indicate PIR detection, a green LED flashes to indicate ultrasonic
detection. You may hold
P
or for 2 seconds while in test mode to test the current
sensitivity of that specific technology.
Restore Default Settings
Press and hold and
P
until all
IL
blink slowly (about 7 seconds). This will restore ALL of the
sensor’s settings back to their defaults.
Off-While-Occupied
When Off-While-Occupied is Enabled: After manual shutoff, the sensor will keep lights off as long
as the space is occupied and the timeout has not expired. This setting is best for rooms where
presentations are given and lights may be kept off during occupancy. This is the default setting.
When Off-While-Occupied is Disabled: After manual shutoff, the sensor will keep lights off for
25seconds before looking for motion. If motion is detected, the lights will turn back on. This
setting is best for high‑traffic areas like bathrooms and hallways.
Change Setting:
1. Press and hold and
P
at the same time until an
IL
begins to flash (about 3 seconds).
2. Tap
P
to cycle to your desired setting.
3. Press and hold
P
until the
IL
goes solid to lock your selection.
Setting Fixed ALD Level
1. a. For Circuit 1: Press and hold
M
and until the
IL
begins to flash (about 3 seconds).
b. For Circuit 2: Press and hold
M
and
P
until the
IL
begins to flash (about 3 seconds).
2. The Ambient Light Detect light level will now be displayed on the
IL
. Tap
M
to cycle to
your desired setting.
3. Press and hold
M
until the
IL
goes solid to lock your selection.
To display current settings, tap the Timeout ( ), Sensor Mode (
M
), Ultrasonic Sensitivity ( ),
or PIR Sensitivity (
P
) button. The indicator LED (
IL
) that corresponds to the current setting will
illuminate.
• Timeout and Sensor Mode settings may have different settings for each circuit. In this case, the
LED for Circuit 1 settings will illuminate, followed by the LED for Circuit 2 settings.
1
Press and hold the desired programming button ( ,
M
, , or
P
) until an
IL
begins to flash
(about 3 seconds). This will change settings for BOTH circuits.
• Timeout ( ) and Sensor Mode (
M
) may be adjusted independently for EACH circuit. Holding
or
M
AND
T
1
or
T
2
simultaneously will program settings for that specific circuit.
Light Level
High: turns lights ON unless room is very bright
Medium
Low (Default when in ALD Fixed mode)
Minimum: turns lights ON only when room is dark
IL
Off-While-Occupied Disabled
Off-While-Occupied Enabled (Default)
IL
IL
Indicator LEDs
Circuit 1
Tap button
(tap on/off)
Circuit 2
Tap button
(tap on/off)
Timeout Button
1
30 minutes
15 minutes
5 minutes
1 minute
T
1
m30
15
5
1
Occ
Lrn
Fixd
Vac
Mode
Hi
Med
Low
Off
Hi
Med
Low
Min
PIR
Ultrasonic Transducers
Sensor LED (behind lens)
Pulses green for ultrasonic and amber
for PIR detection during Test mode.
T
2
Default settings
are shown in bold
Sensor Mode Button
1
Occupancy (Auto-ON / Auto-OFF)
2
Occupancy with Learning ALD
3
Occupancy with Fixed ALD
4
Vacancy (Manual-ON / Auto-OFF)
2
M
Ultrasonic Sensitivity
Button
High
Medium
Low
Off
PIR Sensitivity
Button
High
Medium
Low
Minimum
P
PIR Lens