Cut Sheet

Maestro RF 010 V Sensor Dimmer / RF Sensor Switch SensorVive
3691097a 3 01.24.19
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Specifications
Regulatory Approvals
• UL
® Listed to U.S. and Canadian safety requirements
Complies with Title 20 and Title 24 Section 110.9
Power
Operating voltage: 120 / 277 V~ 50 / 60 Hz,
8 A (USA), 120 V~ 50 / 60 Hz, 8 A (Canada) of
0 –10 V- electronic fluorescent ballasts or LED
drivers for sensor dimmer, and all lighting loads for
sensor switch
Loads
Sensor Dimmer
Works with all ballasts and drivers that provide a
current source compliant to IEC 60929 Annex E.2,
and whose inrush current does not exceed NEMA
410 standards for electronic ballast / driver loads of
8 A steady state current
Supports Electronic Off functionality for voltages
less than 0.5 V
50 mA max sink current
Controls up to 25 ballasts or drivers (IEC 60929
Annex E.2 requires the ballast / driver to limit the
current to 2.0 mA maximum)
No minimum load
Sensor Switch
Works with all lighting loads
Environment
Ambient operating temperature: 32 °F to 104 °F
(0°C to 40 °C), 0% 90% humidity, non-condensing;
indoor use only
Warranty
5 Year Limited Warranty
For additional Warranty information, please visit:
www.lutron.com/TechnicalDocumentLibrary/
Sensor_Warranty.pdf
Key Design Features
Dimmer
On a single-tap, lights fade On or Off to previous level
On a double-tap, lights go to full On
Light levels can be fine-tuned by pressing and
holding the dimming rocker until the desired light
level is reached
High-end trim (adjust maximum light level that can be
achieved, for energy savings)
Low-end trim (adjust minimum light level that can be
dimmed down, to prevent flickering lights)
Vive System Communications and Capacity
Maestro Wireless controls communicate with the
Pico remote controls and Radio Powr Savr sensors
through radio frequency (RF).
Receives wireless inputs from up to 10 Pico remote
controls, 10 Radio Powr Savr occupancy / vacancy
sensors, and 1 Radio Powr Savr daylight sensor.
Maestro Wireless local controls must be located
within 60 ft (18 m) line-of-sight or 30 ft (9 m) through
walls, of Radio Powr Savr sensors and Pico remote
controls. The 60 ft (18 m) range is not reduced by a
ceiling tile obstruction.
Additional Information on Sensors
For more information, please see
www.lutron.com/occvacsensors
Lutron Customer Assistance: 1.844.LUTRON1