Cut Sheet
Vacancy Light Level Preset (Available for products with M6 revision software or later):
1. Press the Raise / Lower Rocker until LED 4 begins to blink.
Note: LED 7 will also be blinking indicating that the product is in SCM.
2. Press the Tap Button once in order to determine the current preset setting. An LED will begin to blink quickly
indicating the current preset setting.
3. Press the Raise / Lower Rocker to adjust the preset setting. The position of the quickly blinking LED will move
indicating the selected preset setting. Please note that any incremental or decremental steps between LEDs will cause
the percentage of the load to vary between the percentages listed in the table below. In order to set the preset to Off
press the Raise / Lower Rocker until LED 1 begins to blink then release. Next press the Raise / Lower Rocker and
continue holding for a period of five seconds. LEDs 1, 2 and 3 will begin scrolling indicating that the preset has been
set to Off.
4. Press the Tap Button once to return to the SCM Menu.
LED
Position
Vacancy
Light Level Preset
4 50% of Load
3 34% of Load
2 17% of Load
1 1% of Load
Scrolling 1, 2, 3 Off (Default)
LED 7: System Configuration Mode
LED 4: Highest Vacancy Light Level
LED 1: Lowest Vacancy Light Level
How to Save Settings and Exit SCM
1. Press and Hold the Tap Button for 4 seconds to exit and save the APM.
Note: If you wait 1 minute the dimmer will automatically exit from APM, however settings will not be saved.
Unlocking the Vacancy Light Level Preset:
1. Press the Lower Rocker until the bottom LED is flashing quickly. Release the lower button and press and hold the
lower button again for approximately 3 seconds or until LEDs 1, 2, and 3 start scrolling. Please note that the light
will remain at its minimum output when you perform this action.
2. Press the Tap Button once to return to the SCM Menu.
11 Technical Support — 1.844.LUTRON1