Cut Sheet
Job Name:
Job Number:
Model Numbers:
PageSPECIFICATION SUBMITTAL
369-143 L 5 03.01.12
RF Local ControlsMaestro WirelessR Designer-style: Maestro
R
Switch Load Type and Capacity
Neutral Required
No Neutral Required
Control Voltage Load Type Minimum
Load
Maximum Load
Not
Ganged
End of
Gang
Middle of
Gang
MRF2-8ANS-120
1,3
120 V~
Lighting 25 W 8 A 6.5 A 5 A
Fan
Motor
0.2 A
1/4 HP
5.8 A
1/4 HP
5.8 A
1/6 HP
4.4 A
MRF2-6ANS
1
120 V~
Lighting 25 W 6 A 5 A 3.5 A
Fan
Motor
0.2 A
1/10 HP
3 A
1/10 HP
3 A
1/10 HP
3 A
MRF2-6ANS-277
2
277 V~ Lighting 25 W 6 A 5 A 3.5 A
Control Voltage Load Type Minimum
Load
Maximum Load
Not
Ganged
End of
Gang
Middle of
Gang
MRF2-8S-DV
2
120–277 V~
Incandescent/
Halogen
25 W 8 A 8 A / 7 A
4
7 A
120–277 V~
Fluorescent/
LED/CFL
40 W
(LUT-MLC)
5
8 A 8 A / 7 A
4
7 A
120 V~
Fan
Motor
0.4 A
1/10 HP
3 A
1/10 HP
3 A
1/10 HP
3 A
1
Switch Load Type: MRF2-8ANS-120 is designed for use with permanently installed lighting loads and with fan motor loads up to 1/4 HP (5.8 A).
MRF2-6ANS is designed for use with permanently installed lighting loads and with fan motor loads up to 1/10 HP (3 A).
MRF2-8S-DV is designed for use with permanently installed lighting loads and with fan motor loads up to 1/10 HP (3 A, 120 V~ only).
2
Switch Load Type: MRF2-6ANS-277 and MRF2-8S-DV are designed for use with permanently installed lighting loads.
3
For loads larger than 8 A @ 120 V~, the MRF2-8ANS-120 switch can be used with the PHPM-SW-DV-WH power booster. For loads larger than the MRF2-6ANS-277
capacity of 6 A @ 277 V~, the MRF2-8ANS-120 can also be used with the PHPM-SW-DV-WH power booster to switch 277 V~ loads. Please note that in this applica-
tion, the MRF2-8ANS-120 switch is providing an input at 120 V~ and the power booster is switching 277 V~.
4
Maximum load for double gang application is 8 A. Triple gang application derates maximum load to 7 A.
5
The LUT-MLC ensures proper function with certain fluorescent, CFL, and LED load types.
5