Cut Sheet
Job Name:
Job Number:
Model Numbers:
PageSPECIFICATION SUBMITTAL
369-143 L 3 03.01.12
RF Local ControlsMaestro WirelessR Designer-style: Maestro
R
Dimmer Load Type and Capacity
Neutral Required
No Neutral Required
Control Voltage Load
Type
Minimum
Load
Maximum Load
Not
Ganged
End of
Gang
Middle of
Gang
MRF2-6ND-120
1,2,4
120 V~
Incand. 25 W 600 W 500 W 400 W
MLV
2
25 W / VA
450 W /
600 VA
400 W /
500 VA
300 W /
400 VA
MRF2-6ELV
2
120 V~ ELV
2
5 W 600 W 500 W 400 W
MRF2-F6AN-DV
3,5
120–277 V~ Lighting
1 ballast
0.05 A
6 A 5 A 3 A
Control Voltage Load
Type
Minimum
Load
Maximum Load
Not
Ganged
End of
Gang
Middle of
Gang
MRF2-600M
1,4
120 V~ Incand. 50 W 600 W 500 W 400 W
MRF2-6MLV
1,2,4
120 V~ MLV
2
50 VA
450 W /
600 VA
400 W /
500 VA
300 W /
400 VA
MRF2-10D-120
1,2,4
120 V~
Incand. 50 W 1000 W 800 W 650 W
MLV
2
50 W / VA
800 W /
1000 VA
600 W /
800 VA
500 W /
650 VA
1
Dimmer Load Type: MRF2-6ND-120, MRF2-6MLV and MRF2-10D-120 are designed for use with permanently installed incandescent, magnetic low-voltage, or tung-
sten halogen only. MRF2-600M is designed for use with permanently installed incandescent or tungsten halogen only. MRF2-6ELV is designed for use with permanently
installed electronic low-voltage only. Do not install dimmers to control receptacles or motor-operated appliances.
2
Low-Voltage Applications: Use MRF2-6ND-120, MRF2-6MLV and MRF2-10D-120 with magnetic (core and coil) low-voltage transformers only. Not for use with elec-
tronic (solid-state) low-voltage transformers. Use MRF2-6ELV with electronic (solid-state) low-voltage transformers only. Operation of a low-voltage circuit with lamps
inoperative or removed may result in transformer overheating and premature failure. Lutron strongly recommends the following:
• Do not operate low-voltage circuits without operative lamps in place.
• Replace burned-out lamps as quickly as possible.
• Use transformers that incorporate thermal protection or fused transformer primary windings to prevent transformer failure due to overcurrent.
3
Can control the following power boosters / load interfaces: Phase-adaptive Power Modules (PHPM-WBX-DV-WH), 3-wire Fluorescent Power Modules (PHPM-3F-DV-WH),
Tu-WireR Fluorescent Power Modules (PHPM-PA-DV-WH), and 0–10 V (GRX-TVI).
4
Can control the following power booster/load interface: Hi-Power 2
•
4
•
6T Boosters (HP-2, HP-4, HP-6) for control of most popular lighting sources including LutronR
3-wire line voltage control fluorescent dimming ballasts (Hi-lumeR, Hi-lume Compact SET, Eco-10R, and EcoSystemR).
5
Dimmer Load Type: MRF2-F6AN-DV is designed for use with permanently installed 3-wire line voltage control fluorescent ballasts or LED drivers only (Hi-lumeR,
Hi-lume Compact SET, Eco-10R, and EcoSystemR).
3