Cut Sheet

Job Name:
Job Number:
Model Numbers:
PageSPECIFICATION SUBMITTAL
369-143 L 10 03.01.12
RF Local ControlsMaestro WirelessR Designer-style: Maestro
R
Single Location Installation
MRF2-8S-DV
*
Brass
Black
Blue - unused, tighten
1
Optional
Green
Ground
Hot/Live
Neutral
Dimmer / Switch
Dimmer / Switch
Wiring Diagrams
Multi-Location Installation
2
MRF2-8S-DV
4,*
with MA-AS / MA-AS-277 or MSC-AS / MSC-AS-277
Brass
Black
Blue
Green
Ground
Brass
Black
Blue
Green
Ground
Brass
Black
Blue
Green
Ground
Hot/Live
Neutral
Companion Dimmer/ Switch Companion Dimmer/ Switch
Load
Load
120 V~
3
60 Hz
or
277 V
~
3
60 Hz
120 V~
3
60 Hz
or
277 V
~
3
60 Hz
LUT-MLC*
1
When using controls in single location installations, tighten the blue terminal without any wires attached. DO NOT connect the blue terminal to any other wiring or
to ground.
2
Up to 9 MaestroR Companion Dimmers / Switches may be connected to the Maestro WirelessR Dimmer / Switch. Total blue terminal wire length may
be up to 250 ft (76 m).
3
120 V~ : MRF2-6ND, MRF2-6ANS-120, MRF2-8ANS-120, MRF2-6ELV-120
277 V~ : MRF2-6ANS-277, MRF2-8S-DV
4
Requires MA-AS / MSC-AS for 120 V~ applications, and MA-AS-277 / MSC-AS-277 for 277 V~ applications.
Optional
*
A LUT-MLC ensures proper function when fluorescent, CFL, or LED
loads are used. Install the LUT-MLC inside a load fixture or in a
separate J-box of the circuit.
LUT-MLC*
10