Cut Sheet

®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Radio Powr SavrT Wireless Wall-Mount Occupancy and Vacancy Sensors
369481d 7 04.01.13
Installation Overview
Sensor Placement
•Themountingheightofthesensorshouldbebetween6ftand8ft(1.6mand2.4m)
•Forsmallerroomslessthan12ftx12ft(3.7mx3.7m),detectionmaybeimprovedbymountingthesensorat
6ft(1.8m)fromtheoor.
•Theabilitytodetectmotionrequiresthatthesensorhaveline-of-sightofallroomoccupants.Thesensormust
have an unobstructed view of the room. DO NOTmountbehindorneartallcabinets,shelves,hangingxtures,
etc.Thesensorcannotdetectoccupantsthroughglassobjectssuchaspatioorshowerdoors.
•Hotobjectsandmovingaircurrentscanaffecttheperformanceofthesensor.Toensureproperoperation,the
sensorshouldbemountedatleast4ft(1.2m)awayfromlightbulbsandHVACvents.
•The performance of the sensor depends on a temperature differential between the ambient room temperature
andthatofroomoccupants.Warmerroomsmayreducethesensor’sabilitytodetectoccupants.
•Distancebetweenlocalloadcontrolsandsensorshouldnotexceed60ft(18m)lineofsightor30ft(9m)
through walls.
7