Radio Powr SavrTM Wireless Occupancy and Vacancy Sensors
369327 Rev A 3 10.07.10
Range Diagrams
Sensor Coverage with an 8 ft (2.4 m) Ceiling
15 ft
(4.6 m)
12 ft
(3.7 m)
9 ft
(2.7 m)
6 ft
(1.8 m)
3 ft
(0.9 m)
0 ft
(0 m)
3 ft
(0.9 m)
6 ft
(1.8 m)
9 ft
(2.7 m)
12 ft
(3.7 m)
15 ft
(4.6 m)
Radius of Coverage at Floor
Sensor
Occupant
18 x 18 ft (5.5 x 5.5 m)
Maximum Room Dimensions
for Complete Coverage when
mounted on an 8 ft (2.4 m) Ceiling
13 ft (4.0 m)
Radius of Coverage at Floor when
mounted on an 8 ft (2.4 m) Ceiling
Ceiling
Floor
8 ft
(2.4 m)
Ceiling
height
Instructions
Sensor Coverage Chart (for sensor mounted in center of room)
Ceiling
Height
Max. Room Dimensions
for Complete Coverage
Radius of Coverage
at Floor
8 ft (2.4 m) 18 x 18 ft (5.5 x 5.5 m) 13 ft (4.0 m)
9 ft (2.7 m) 20 x 20 ft (6.1 x 6.1 m) 14.5 ft (4.4 m)
10 ft (3.0 m) 22 x 22 ft (6.7 x 6.7 m) 16 ft (4.9 m)
12 ft (3.7 m) 26 x 26 ft (7.9 x 7.9 m) 19 ft (5.8 m)
* Multiple sensors can be added for extended coveragerefer to product specification
submittals of receiving device to determine system limits.