Cut Sheet

SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
369974a 9 11.05.15
ThermostatL-HWLV2-WIFI
LutronR
Conventional Systems
1H/1C System (1 transformer) 1H/1C System (2 transformers)
Heat Only System Heat Only System With Fan
Heat Only System (Series 20) Cool Only System
2H/2C System (1 transformer) 2H/2C System (2 transformers)
Wiring Guide (for use with 24 V~ common)
Continued on next page...
C 24 V~ common
Rc Power
R R and Rc joined by jumper
W Heat relay
Y Compressor contactor
G Fan relay
S1 / S1 Optional remote sensor
C 24 V~ common (cooling transformer)
Rc Power (cooling transformer)
R Power (heating transformer)
W Heat relay
Y Compressor contactor
G Fan relay
S1 / S1 Optional remote sensor
C 24 V~ common
Rc Power
R R and Rc joined by jumper
W Heat relay
S1 / S1 Optional remote sensor
C 24 V~ common
Rc Power
R R and Rc joined by jumper
W Heat relay
G Fan relay
S1 / S1 Optional remote sensor
C 24 V~ common
Rc R and Rc joined by jumper
R Series 20 valve terminal “R”
W Series 20 valve terminal “B”
Y Series 20 valve terminal “W”
S1 / S1 Optional remote sensor
C 24 V~ common
Rc Power
R R and Rc joined by jumper
Y Compressor contactor
G Fan relay
S1 / S1 Optional remote sensor
C 24 V~ common
Rc Power
R R and Rc joined by jumper
W Heat relay 1
Y Compressor contactor 1
G Fan relay
W2 Heat relay 2
Y2 Compressor contactor 2
S1 / S1 Optional remote sensor
C 24 V~ common (cooling transformer)
Rc Power (cooling transformer)
R Power (heating transformer)
W Heat relay 1
Y Compressor contactor 1
G Fan relay
W2 Heat relay 2
Y2 Compressor contactor 2
S1 / S1 Optional remote sensor
9