Remote Power Modules
6www.lutron.com Technical support: U.S.A.: 800.523.9466
Europe: +44.(0)20.7680.4481
Address Switch Position
HW-RPM-4A-120, HW-RPM-4A-230,
HW-RPM-4E-230-CE, HW-RPM-4FSQ-120,
HW-RPM-4J-120, HW-RPM-4R,
HW-RPM-4U-120, HW-RPM-4U-230-CE,
HW-RPM-4U-240:
Position Module Output/Purpose
0 All outputs OFF
1–8 Address for normal operation
9 A Not used
9 B Output 1 ON; Use for temporary lighting and
zone testing
9 C Output 2 ON; Use for temporary lighting and
zone testing
9 D Output 3 ON; Use for temporary lighting and
zone testing
9 E Output 4 ON; Use for temporary lighting and
zone testing
9 F All outputs ON; Use for temporary lighting and
zone testing
HW-RPM-4M, HW-RPM-4M-230:
Position Module Output/Purpose
0 All relays OFF
1–8 Address for normal operation
9 A–D Not used: All outputs OFF
9 E All raise relays ON; Use for directional motor
testing
9 F All lower relays ON; Use for directional motor
testing
Diagnostic LED Status
HW-RPM-4A-120, HW-RPM-4A-230,
HW-RPM-4E-230-CE, HW-RPM-4FSQ-120,
HW-RPM-4J-120, HW-RPM-4R,
HW-RPM-4U-120, HW-RPM-4U-230-CE,
HW-RPM-4U-240:
LED Status Possible Cause
Off No power or defective module
1 blink per second
(“Heartbeat”)
Normal operation
1 blink per 7 seconds
(“Lighthouse”)
Not communicating with
processor:
• Open control harness
• Module set on invalid or
diagnostic address
• System not properly configured
or addressed in HomeWorks
®
software
4 blinks; pause; repeat Module in manual override
10 blinks per second Zone error on one or more
outputs
Zone Diagnostic LED Status
HW-RPM-4E-230-CE, HW-RPM-4A-120,
HW-RPM-4J-120, HW-RPM-4A-230 only:
Zone LED Status Load Status Description
Off OFF Normal; Load Off
Continuously on ON Incandescent/electronic
dimming
1 blink per
second
ON Magnetic dimming
Error Codes
1 blink; pause;
repeat
OFF Load short circuit
1
2 blinks; pause;
repeat
OFF Inductive load
2
3 blinks; pause;
repeat
ON Full Shorted component
3
4 blinks; pause;
repeat
OFF Overload
1
10 blinks per
second
All outputs
OFF
Multiple errors
4
1
Locate and repair fault. Cycle power to RPM.
2
Check software configuration. MLV load detected with ELV
software setting.
3
Replace RPM. Internal device (FET) shorted.
4
Multiple errors exist on this output. The relay has opened to
protect the modules and all 4 outputs will be off.
Enlarged view of Address Switch