Cut Sheet

product specifications
10.27.15369547d
Remote Power Modules
2www.lutron.com Technical support: U.S.A.: 800.523.9466
Europe: +44.(0)20.7680.4481
Specifications
Model Numbers HW-RPM-4A-120, HW-RPM-4A-230, HW-RPM-4E-230-CE, HW-RPM-4FSQ-120, HW-RPM-4J-120,
HW-RPM-4M-120, HW-RPM-4M-230, HW-RPM-4R, HW-RPM-4U-120, HW-RPM-4U-230-CE,
HW-RPM-4U-240
Power HW-RPM-4A-120, HW-RPM-4FSQ-120, HW-RPM-4J-120, HW-RPM-4M-120, HW-RPM-4U-120:
120 V~ 50 / 60 Hz
HW-RPM-4A-230, HW-RPM-4M-230, HW-RPM-4U-230-CE, HW-RPM-4U-240:
220–240 V~ 50 / 60 Hz
HW-RPM-4R: 100–277 V~ 50 / 60 Hz
Number of Outputs 4
Regulatory Approvals UL
®, CSA, NOM
Environment Ambient operating temperature : 32 °F to 104 °F (0 °C to 40 °C), 0 to 90% humidity, non-condensing.
Indoor use only.
Cooling Passive cooling.
Heat Generated
Fully Loaded
HW-RPM-4A-120, HW-RPM-4A-230, HW-RPM-4E-230-CE, HW-RPM-4J-120: 90 BTUs per hour.
HW-RPM-4FSQ-120, HW-RPM-4M-120, HW-RPM-4M-230, HW-RPM-4R: 18 BTUs per hour.
HW-RPM-4U-120, HW-RPM-4U-230-CE, HW-RPM-4U-240: 70 BTUs per hour.
Line-Voltage
Connections
Separate line-voltage feeds at the DIN rail terminal blocks for each RPM. Terminal blocks should be
tightened to 3.5 in-lb to 5.0 in-lb (0.40 N•m to 0.57 N•m).
Low-Voltage
Communications
Communication harness (included).
Wiring Terminal blocks will accept one 18 AWG to 10 AWG (1.0 mm
2
to 6.0 mm
2
) wire or two
18 AWG to 16AWG (1.0 mm
2
to 1.5 mm
2
) wires.
HW-RPM-4M-120, HW-RPM-4M-230, HW-RPM-4R: Require the installation of four additional gray
terminal blocks (included) and three additional black terminal blocks (included) to be mounted on to
the DIN rail assembly.
HW-RPM-4R gray terminal blocks accept one 18AWG to 8 AWG (1.0 mm
2
to 10 mm
2
) wire or two
16 AWG to 12 AWG (1.5 mm
2
to 4.0 mm
2
) wires.
Addressing Manual rotary switch. Counts as 1 of 8 RPM addresses per module interface.
Diagnostics LED provided to indicate proper communications with module interface.
ESD Protection Meets or exceeds the IEC 61000-4-2 standard.
Surge Protection Meets or exceeds ANSI/IEEE standard c62.41.
Air Gap HW-RPM-4U-120, HW-RPM-4U-230-CE HW-RPM-4A-120, HW-RPM-4A-230, HW-RPM-4J-120,
HW-4FSQ-120, HW-RPM-4M-230: Provided when all four circuits are off.
HW-RPM-4R: Individual output airgap provided when each circuit is off.
Fail-Safe Operation Rotary switch on the RPM allows for manual operation of each load.
Dimensions 3
7
8 in (99 mm) wide × 7 in (178 mm) high
Lamp Buzz Lamp debuzzing coils (Lutron
® model HW-HIFC-10-2, LDC-10-TCP, LDC-16-TCP) are available from
Lutron to reduce lamp filament buzzing.
Interface Suppression EMI/RFI suppression circuitry
Warranty www.lutron.com/TechnicalDocumentLibrary/Warranty.pdf