Cut Sheet

®
SPECIFICATION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
Lutron GRX-TVI Power Interfaces
369247e 5 07.07.16
L2/H2 100-277 V~
LUTRON
LUTRON
GRX-TVI
To additional ballast / drivers
Note: Ballast / driver must
provide a 0—10 V- source
only!
EARTH / GROUND
CONNECTIONS
GRAFIK EyeR
Control Unit
1
OR
Dimmed Line /
Dimmed Hot, DL / DH
Switched Line / Hot
Line / Hot
Line / Hot
Line / Hot
Earth / Ground
Earth / Ground
NOTICE: 0—10 V- Control Signal Wires
— DO NOT CONNECT TO LINE VOLTAGE.
LutronR is not liable for damage due to miswiring.
Use 20 A (10 A CE)
maximum circuit
breaker / MCB
Neutral
Neutral
Neutral
Distribution
Panel A
Distribution
Panel B
Neutral
Earth / Ground
Earth / Ground
Wiring Diagram B: HomeWorksR Wallbox Power Module / GRAFIK EyeR Control Unit
— 2 Distribution Panels / 2 Feeds
HomeWorksR Wallbox
Power Module
1
(HWI-WPM-6D)
L2 / H2 terminals are tied to each other
internally. It is the Line / Hot feed that
powers the internal circuitry of the
GRX-TVI. Use the appropriate voltage
in the range of 100277 V~. Refer to
the Note on the first page of the
GRX-TVI Specification Submittal.
L1 / H1 is the Line / Hot feed that
powers the Switched Line / Hot output
to the load. Use any voltage in the
range of 100277 V~.
Note: If the voltage of the ballast / driver is
different from the voltage of the control device,
they should come from different distribution panels
(demonstrated above).
If the control side plus the load side current is
greater than the circuit breaker rating, and the
voltages of load and control are the same level,
follow Diagram O.
Line / Mains Voltage:
100—277 V~
0—10 V-
Ballast / Driver
2
0—10 V-
Ballast / Driver
2
1
Control units must be rated for the Distribution Panel A Line / Mains
voltage utilized.
2
Ballasts / drivers must be rated for the Distribution Panel B Line / Mains
voltage utilized.
Line / Mains Voltage:
100—240 V~
Wiring Diagrams (continu ed)
5